Q Commands                          NOTE : Data is expressed in decimal notation.
C
ommunica
-
tion
Num-
ber.(HEX)
Function Adjustment Range Min.
Setting
Unit
Initial
Value
Write
During
O
pe
r
atio
n
EEP
ROM
FA00 Command 1 (2-wire RS485) 10 to 65535 0yesNone
FA01 Frequency command value (2-
wire RS485) 10 to Max. frequency
()
0.01Hz 0 yes None
FA03 Operation panel operation
frequency *2Low-limit frequency
() to High-limit
frequency ()
0.01Hz 0 yes Available
FA04 Command 1 (4-wire RS485) 10 to 65535 0yesNone
FA05 Frequency command value (4-
wire RS485) 10 to Max. frequency
()
0.01Hz 0 yes None
FA10 Panel key selection 40: Main unit
1: Comunication
0yesNone
FA11 External communication key
data 40 to 65535 0yesNone
FA20 Command 2 (2-wire RS485) 10 to 65535 0yesNone
FA22 Command 2 (4-wire RS485) 10 to 65535 0yesNone
FA30 Torque command value (2-wire
RS485)
-250.00 to 250.00 0.01% 0 yes None
FA32 Torque command value (4-wire
RS485)
-250.00 to 250.00 0.01% 0 yes None
FA50 Terminal output data 30 to 255 1 0 yes None
FA51 FM analog output data 30 to 2047
(11-bit resolution)
10yesNone
FA52 AM analog output data 30 to 2047
(11-bit resolution)
10yesNone
FA53 MON1 analog output data 30 to 2047
(11-bit resolution)
10yesNone
FA54 MON2 analog output data 30 to 2047
(11-bit resolution)
10yesNone
FA65 Select display by communica-
tion 40 to 2 1 yes Available
FA66 Numerical display data 40-9999 1 0 yes Available
FA67 Decimal point position 40 to 2 0 yes Available
FA68 LED data for unit 0 40 to 3 0 yes Available
FA70 ASCII display data 1
First digit from left 40 to 127 100
(‘d’)
yes Available
FA71 ASCII display data 1
Second digit from left 40 to 255 65
(‘A’)
yes Available
FA72 ASCII display data 1
Third digit from left 40 to 255 116
(‘t’)
yes Available
FA73 ASCII display data 1
Fourth digit from left 40 to 127 65
(‘A’)
yes Available
FA74 LED data for unit1 40 to 3 0 yes Available
FA75 ASCII display data 2
First digit from left 40 to 127 48
(‘0’)
yes Available
FA76 ASCII display data 2
Second digit from left 40 to 255 48
(‘0’)
yes Available
FA77 ASCII display data 2
Third digit from left 40 to 255 48
(‘0’)
yes Available
FA78 ASCII display data 2
Fourth digit from left 40 to 127 48
(‘0’)
yes Available
FA79 LED data for unit 2 40 to 3 0 yes Available
FA80 Block communication mode 40 to 1 0 yes Available