Toshiba TOSVERT VF-AS1 instruction manual Inv-No, Data SUM

Models: TOSVERT VF-AS1 VF-AS1

1 73
Download 73 pages 18.65 Kb
Page 10
Image 10

efesotomasyon.com -Toshiba inverter,drive,servo,plc

E6581315

Data returned when data is not processed normally (ASCII mode)

In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type num- ber is returned to the computer in addition to the checksum. At time of broadcast communication of the binary mode, returning of data is not executed except for the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This is because there will be a risk that the returned data may be deformed.

 

 

 

Omissible

 

 

 

 

 

 

 

 

Omissible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3.5bytes

“(“

 

INV-NO

“N” or “n”

 

DATA

"&"

SUM

 

 

")"

CR

Blank)

(28H)

 

2 bytes

(4EH)

(6EH)

 

4 bytes

(26H)

2 bytes

 

 

(29H)

(0DH)

 

 

 

 

 

 

 

 

Checksum area

 

 

 

 

 

 

 

Omissible

(3.5bytes

Blank)

“(“ (1 byte)

: Start code in ASCII mode

“N” or “n” (1 byte)

:Communication error command ... This is also used for the checking of inverter trip.

 

“N” for the normal communication and “n” during the inverter trip.

INV-NO (2 bytes)

: Inverter number (omitted if it is not found in the data received) ... 00 (30H, 30H) to 99 (39H,

 

39H)

 

If the inverter number matches up with that specified using a parameter, data will be return-

 

ed to the computer. In broadcast communication, only the destination inverter (with a num-

 

ber matching up with the smallest effective number) returns data to the computer.

Data (4 bytes)

: Error code (0000~0004)

 

0000 ... Impossible to execute (Although communication is established normally, the

 

command cannot be executed because it is to write data into a parameter whose

 

setting cannot be changed during operation (e.g., maximum frequency) or the

 

EEPROM is faulty.)

 

0001 ... Data error (The data is outside the specified range or it is composed of too many

 

digits.)

 

0002 ... Communication number error (There is no communication number that matches.)

 

0003 ... Command error (There is no command that matches.)

 

0004 ... Checksum error (The checksum result differs.)

“)” (1 byte)

: Stop code ... This code is omitted if it is not found in the data received.

„Examples:

(N0000&5C)CR... Impossible to execute (e.g., a change of maximum frequency data during opera- tion)

(N0001&5D)CR... Data error (Data is outside the specified range.)

(N0002&5E)CR... No communication number (There is no communication number that matches.) (N0003&5F)CR... There is no command that matches. (Commands other than the R, W and P

commands)

(Ex.: L, S, G, a, b, m, r, t, w ...) (N0004&60)CR... Checksum error (The checksum result differs.) No data returned ... Format error or invalid inverter number

9

Page 10
Image 10
Toshiba TOSVERT VF-AS1 instruction manual Inv-No, Data SUM