E6581315

„Alarm information monitor (FC91)

Bit

Specifications

0

1

Remarks

(Code displayed on the panel)

 

 

 

 

0

Over-current alarm

Normal

Alarming

 flickering

1

Inverter overload alarm

Normal

Alarming

 flickering

 

2

Motor overload alarm

Normal

Alarming

 flickering

 

3

Overheat alarm

Normal

Alarming

 flickering

 

4

Overvoltage alarm

Normal

Alarming

 flickering

 

5

Main circuit undervoltage alarm

Normal

Alarming

-

6

(Reserved)

-

-

-

7

Low current alarm

Normal

Alarming

-

8

Over-torque alarm

Normal

Alarming

-

9

Braking resistor overload alarm

Normal

Alarming

-

 

10

Cumulative operation hours

Normal

Alarming

-

alarm

 

 

 

 

11

(Reserved)

-

-

-

12

(Reserved)

-

-

-

13

(Reserved)

-

-

-

14

At the time of the instant black-

-

Decelerating,

Related:  setting

out, Forced deceleration/stop

stopping

 

 

 

 

15

An automatic stop during the

-

Decelerating,

Related:  setting

lower limit frequency continu-

stopping

 

 

 

 

 

ance

 

 

 

„Cumulative operation time alarm monitor (FE79)

Bit

Specifications

0

1

Remarks

0

Fan life alarm

Normal

Alarm issued

-

1

Circuit board life alarm

Normal

Alarm issued

-

2

Main-circuit capacitor life alarm

Normal

Alarm issued

-

3

User set alarm

Normal

Alarm issued

-

4-15

(Reserved)

-

-

-

55

Page 56
Image 56
Toshiba TOSVERT VF-AS1 „ Alarm information monitor FC91, „ Cumulative operation time alarm monitor FE79