E6581315
9.Parameter data
Explanation of parameters for
Referring to the parameter list
<Example of excerpts from the inverter’s instruction manual>
Title
Communi- cation No.
Function
Adjustment range
Minimum set- |
| |
ting unit | Default | |
(Panel/Communi | setting | |
cation) | ||
|
Write during
running
Refer-
ence
auh | - | History function |
| 1/1 | - | - |
|
au1 | 0000 | Automatic accelera- | 0:Deselect | 1/1 | 0 | Disabled |
|
|
| tion/deceleration | 1:Automatic setting |
|
|
|
|
|
|
| 2:Automatic setting (during |
|
|
|
|
|
|
| acceleration only) |
|
|
|
|
au2 | 0001 | Automatic torque | 0:Deselect | 1/1 | - | Disabled |
|
|
| boost | 1:Automatic torque boost + |
|
|
|
|
|
|
|
|
|
|
|
5.1
5.2
5.3
: | : |
: | : |
acc | 0009 | Acceleration time | 0.1~6000 sec. | 0.1/0.1 *2 | *1 | Enabled |
|
|
| 5.2 |
1 |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| |
|
|
| 0: - |
|
|
|
|
|
|
|
|
|
| 1:50 Hz default setting |
|
|
|
|
|
|
|
|
|
| 2:60 Hz default setting |
|
|
|
|
|
|
|
|
|
| 3:Factory default setting |
|
|
|
|
|
|
|
|
| Factory default | : |
|
|
|
|
|
|
|
typ | 0007 | 10:Acceleration/deceleration | 1/1 | - | Disabled |
|
|
| 5.20 | |
setting |
|
| ||||||||
|
| time setting 0.01 |
|
|
|
|
|
|
| |
|
|
| sec.~600.0 sec. |
|
|
|
|
|
|
|
|
|
| 11:Acceleration/deceleration |
|
|
|
|
|
|
|
|
|
| time setting 0.1 |
|
|
|
|
|
|
|
|
|
| sec.~6000sec. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| : |
|
|
|
|
|
|
|
*1: Default values vary depending on the capacity.
*2: Changing the parameter enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
-The summary of parameter list relating to the communication is as follows.
(1)“Title” means the display on the inverter panel.
(2)“Communication number” is affixed to each parameter that is necessary for designating the parameter for com- munication.
(3)"Adjustment range" means a data range adjustable for a parameter, and the data cannot be written outside the range. The data have been expressed in the decimal notation. For writing the data through the communication function, take the minimum setting unit into consideration, and use hexadecimal system.
(4)"Minimum setup unit" is the unit of a single data (when the minimum unit is
For example, the "minimum setup unit" of acceleration time () is 0.01, and 1 is equal to 0.01s. For setting a data to 10 seconds, transmit 03E8h [10÷0.01=1000d=03E8h] by communication.
(5)If FA09 is set to 0, the acceleration/deceleration time parameters acc, dec, f500, f501, f510, f511, f514, and f515 can be set in units of 0.01 sec.
QAcceleration/deceleration setting time unit (FA09) Communication No. Function name
FA09 | Acceleration/deceleration time unit |
Unit
-
Adjustment range
0:0.01 sec.
1:0.1 sec.
62