E6581315
Terminal board output data (FA50)
The output terminal board on each inverter can be directly controlled with the computer.
To use this function, select functions 92 to 105 in advance for the output terminal function selection parameters f130 to f138, f168andf169. If bit 0 through bit 6 of terminal board output data (FA50) are set with the computer, data specified (0 or 1) can be sent to any output ter- minal.
Data composition of terminal board output data (FA50)
Bit | Output terminal function | 0 | 1 |
0 | Specified data output 1 | OFF | ON |
| (Output terminal no.: 92, 93) |
|
|
1 | Specified data output 2 | OFF | ON |
| (Output terminal no.: 94, 95) |
|
|
2 | Specified data output 3 | OFF | ON |
| (Output terminal no.: 96, 97) |
|
|
3 | Specified data output 4 | OFF | ON |
| (Output terminal no.: 98, 99) |
|
|
4 | Specified data output 5 | OFF | ON |
| (Output terminal no.: 100, 101) |
|
|
5 | Specified data output 6 | OFF | ON |
| (Output terminal no.: 102, 103) |
|
|
6 | Specified data output 7 | OFF | ON |
| (Output terminal no.: 104, 105) |
|
|
7 to 15 | - | - | - |
Example of use: To control only the OUT1 terminal with the computer
To turn on the OUT1 terminal, set the output terminal function selection 1 parameter (f130) to 92 (output terminal function selection 1 (positive logic)) and specify 0001H for FA50.
FA50: | BIT15 |
|
|
|
|
|
|
|
|
|
|
|
|
| BIT0 | |||
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 1 | |
|
|
| ||||||||||||||||
|
|
| 0 |
|
|
| 0 |
|
|
| 0 |
|
|
| 1 |
|
|
|
FM analog output (FA51)
The FM analog terminal on each inverter can be directly controlled with the computer.
To use this function, set the FM terminal meter selection parameter (fmsl) to 31 (communication data output).
This makes it possible to send out the data specified as FM analog output data (FA51) through the FM analog output terminal. Data can be adjusted in a range of 0 to 2047 (resolution of 11 bits). For details, refer to “Meter setting and adjustment” of the instruction manual included with the inverter.
AM analog output (FA52)
The AM analog terminal on each inverter can be directly controlled with the computer.
To use this function, set the AM terminal meter selection parameter (amsl) to 31 (communication data output).
This makes it possible to send out the data specified as AM analog output data (FA52) through the AM analog output terminal. Data can be adjusted in a range of 0 to 2047 (resolution of 11 bits). For details, refer to “Meter setting and adjustment” of the instruction manual included with the inverter.
48