5.1.MODBUS-RTU transmission format

MODBUS-RTU sends and receives binary data without a frame-synchronizing start code and de- fines the blank time to recognize the start of a frame. MODBUS-RTU decides the data that is first received subsequently as the first byte of a frame after a blank time for 3.5 bytes at the on-going communication speed.

5.1.1. Read command (03)

„ Computer → Inverter *The text size is 8 bytes fixed.

 

 

 

Commu-

Commu-

Number

Number

CRC

CRC

 

(3.5bytes

Inverter

Command

nication

nication

of Data

of Data

(3.5bytes

Blank)

No.

 

No.

No.

Groups

Groups

(low)

(high)

Blank)

 

 

(high)

(low)

(high)

(low)

 

 

 

 

 

 

 

 

 

 

03

 

 

00

01

 

 

 

1) Inverter No.. (1 byte)

:Specify an inverter number between 0 and 247 (00H to F7H).

Command processing will be executed only broadcast communication “0” and with those inverters that match set inverter numbers. Data will not be returned if “0” (broadcast communication) and inverter numbers do not match.

2)

Command (1 byte)

: Set the read command (03H fixed).

3)

Communication No.. (2 bytes)

: Set in the order of high to low numbers.

4)

Number of data groups (2 bytes)

: Set the number of data words 0001 (fixed) in the order of high to low numbers.

5)

CRC (2 bytes)

: Set generation results of CRC in the order of low to high numbers.. For the

 

 

method to generate CRC, see “5.2 CRC Generation.” Note that the setting se-

 

 

quence is reversal to that of others.

„ Inverter → Computer (Normal return) *The text size is 7 bytes fixed.

(3.5bytes

Blank)

Inverter

Command

Number of

Read data

Read data

CRC

CRC

No.

 

Data

(high)

(low)

(low)

(high)

 

03

02

 

 

 

 

(3.5bytes

Blank)

1)

Command (1 byte)

: Read command (03H fixed) will be returned.

2)

Number of data

: A number of data bytes (02H fixed) will be returned.

 

 

transmission to the inverters is 2 bytes and 01H fixed.

 

 

turned by the inverters is 1 byte and 02H fixed.

The number of data groups for Note that the number of data re-

3) Read data (2 bytes) : Returned in the order of read data (high) and (low).

„ Inverter → Computer (Abnormal return) *The text size is 5 bytes fixed.

(3.5bytes

Blank)

Inverter No.

Command

Error Code

CRC

CRC

(low)

(high)

 

 

 

 

83

 

 

 

(3.5bytes

Blank)

1)

Command (1 byte)

: 83H fixed (Read command error) (Command + 80H)

2)

Error code (1 byte)

: See “4.3 Transmission errors.”

„ Example: Reading output frequency (During 60Hz operation)

(Computer → inverter)

01 03

FD 00 00 01 B5 A6

(Inverter → computer)

01 03

02 17 70 B6 50

„Example: Data specification error

(Computer → inverter)

01 03

FD 00 00 02 F5 A7

(Inverter → computer)

01 83

03 01 31

30