E6581315
51
Output terminal board status (FD07, FE07)
Output terminal board status (current status): “Communication Number FD07”
Output terminal board status (status immediately before the occurrence of a trip): “Communication
Number FE07”
Using terminal function selection parameters, functions can be assigned individually to the termi-
nals on the output terminal board.
When using a terminal as a monitoring terminal, check beforehand the function assigned to each
terminal.
Data composition of output terminal board status (FD07, FE07)
Bit Terminal name Function (parameter title) 0 1
0 OUT1 Output terminal function selection 1 (f130)
1 OUT2 Output terminal function selection 2 (f131)
2 FL Output terminal function selection 3 (f132)
3 OUT3 Output terminal function selection 4 (f133)
4 OUT4 Output terminal function selection 5 (f134)
5 R1 Output terminal function selection 6 (f135)
6 OUT5 Output terminal function selection 7 (f136)
7 OUT6 Output terminal function selection 8 (f137)
8 R2 Output terminal function selection 9 (f138)
9 R3 Output terminal function selection 10 (f168)
10 R4 Output terminal function selection 11 (f169)
OFF ON
11 to 15 --
Example: Data set for FE07 when both the OUT1 and OUT2 terminals are ON = 0003H
0000000000000011
FE07:
0300
bit0BIT15
Monitoring of the analog input with the computer (FE35 to FE39)
RR terminal board monitor: “Communication Number FE35”
VI/II terminal board monitor: “Communication Number FE36”
RX terminal board monitor: “Communication Number FE37”
AI1 terminal board monitor : “Communication Number FE38”
AI2 terminal board monitor: “Communication Number FE39”
These monitors can also be used as A/D converters irrespective of the inverter’s control.
RR terminal board monitor, VI/II terminal board monitor and AI2 terminal board monitor are capable
of reading the data from external devices in a range of 0.01 to 100.00% (unsigned data: 0H to
2710H).
RX terminal board monitor and AI1 terminal board monitor are capable of reading the data from ex-
ternal devices in a range of -100.00 to +100.00% (signed data: D8F0H to 2710H).
If analog input mode is selected with the frequency setting mode selection parameter, however,
keep in mind that any data entered via an analog terminal is regarded as a frequency command.
efesotomasyon.com -Toshiba inverter,drive,servo,plc