System Configurations

When more than one chiller plant is operating, finding the right location for the differential pressure sensor can be difficult. The point of lowest pressure in the system shifts depending on which loads are using the most water. It will probably be necessary to have a number of differential pressure sensors in the distribution loop. In that instance, the control system determines the lowest differential pressure signal and uses it to determine what speed signals to send to the distribution pumps. Sending the same speed signal to both distribution pumps is simple and will prevent the pumps from “fighting” each other for the load. However, it will likely result in more chillers operating than would be required to meet the load (more on this below). There is one exception: If only one chilled-water plant has an operating chiller, the distribution pump associated with that plant should be the only one operating.

Chiller sequencing in a double-ended decoupled system

In addition to pump control, the sequencing of chillers must be integrated between the two plants. With a double-ended plant, it is possible to have one plant operating in deficit flow and the other with sufficient surplus flow to meet the needs of the loads (load/flow imbalance). In other words, a sufficient number of chillers are operating to meet the load, but the distribution pumps are not delivering the flow to where it is needed. There are two solutions to this problem:

1Adjust the speeds of the distribution pumps to move the water to where it is needed. This solution is simple in concept but difficult in application and will not be covered here. It increases complexity and should be considered carefully prior to implementation. If this is attempted, both distribution pump speeds should be changed slowly, and in opposite directions (increase one, decrease the other).

2Allow each of the plants to make start/stop decisions based on the flow in its decoupler. In this case, the needs of the loads will be met; however, more chillers may be running than would otherwise be required.

Starting chillers. When deficit flow is detected at a chilled-water plant, a chiller associated with that plant should be started. This should start chillers in the plant closest to the loads using the most water and help avoid the load/ flow imbalance described above. Deficit flow can be detected by either of the common flow detection methods. (See “Flow-based control” on page 51.) Note that this limits the operator's flexibility to preferentially start chillers in the plant further from the load (preferential start may be desirable to load the plant with the most efficient chillers first, for example).

Stopping chillers. On a single-plant decoupled system, surplus flow through the decoupler pipe is the normal operating mode. When the surplus flow exceeds the flow of one of the chillers in the plant by a fixed percentage, that chiller and its pump can be stopped and the plant will still be creating surplus flow. On double-ended plants this same logic can be used; however, a chiller should only be shut off when both plants have sufficient surplus to shut off a chiller. Only one chiller should be stopped at this time, and it should be the one in the plant with the most surplus flow. Thus, the normal operating mode for a double-ended plant is with one plant in surplus and the other operating

54

Chiller System Design and Control

SYS-APM001-EN

Page 60
Image 60
Trane SYS-APM001-EN manual Chiller sequencing in a double-ended decoupled system

SYS-APM001-EN specifications

The Trane SYS-APM001-EN is an advanced control system designed for HVAC (Heating, Ventilation, and Air Conditioning) applications, specifically tailored to enhance energy efficiency and system performance. This comprehensive solution integrates cutting-edge technologies to optimize climate control in commercial and industrial environments.

One of the main features of the SYS-APM001-EN is its intuitive user interface. The system is equipped with a large, easy-to-read display that provides real-time data on system performance, energy usage, and environmental conditions. This user-friendly interface makes it simple for operators to monitor and adjust settings, ensuring optimal comfort levels and efficient energy consumption.

Another key characteristic of the SYS-APM001-EN is its advanced data analytics capabilities. The system collects and analyzes data from various sensors throughout the building, providing insights into occupancy patterns, equipment performance, and energy consumption trends. This data-driven approach allows facility managers to make informed decisions about system adjustments, predictive maintenance, and energy savings.

The SYS-APM001-EN also boasts robust integration capabilities. It can seamlessly connect with a variety of building management systems (BMS) and other third-party devices. This interoperability enables a cohesive operational ecosystem where HVAC systems can communicate and cooperate with lighting, security, and fire safety systems, enhancing overall building efficiency.

Energy efficiency is a hallmark of the SYS-APM001-EN, as it implements sophisticated algorithms to optimize system operation. These algorithms adjust equipment performance in real-time based on current conditions, thereby reducing energy waste and lowering operational costs. The system is designed to support multiple energy-saving strategies, including demand-controlled ventilation and optimal start/stop scheduling.

Additionally, the SYS-APM001-EN is built with scalability in mind, accommodating facilities of various sizes and configurations. Whether it’s a small office building or a large industrial complex, the system can be tailored to meet specific needs, ensuring that HVAC performance aligns with operational goals.

In conclusion, the Trane SYS-APM001-EN is an innovative HVAC control solution that emphasizes user experience, data-driven decision-making, and energy efficiency. With its advanced features and technologies, it is an essential tool for optimizing building performance and enhancing occupant comfort while reducing environmental impact.