Trane SYS-APM001-EN manual System Design Options, The total system power is now as follows

Models: SYS-APM001-EN

1 114
Download 114 pages 32.43 Kb
Page 38
Image 38
The total system power is now as follows:

System Design Options

The total system power is now as follows:

Table 8. Total system power

Component Power (kW)

Base Case

Low Flow*

 

 

 

Chiller

256.0

292.0

 

 

 

Chilled-water pump

32.0

8.4

 

 

 

Condenser-water pump

25.2

8.8

 

 

 

Cooling tower

24.1

16.0

 

 

 

Total power for chilled-water system

337.3

325.2

 

 

 

*Low-flow conditions represented in Table 5 through Table 8 are 1.5 gpm/ton [0.027 L/s/kW] chilled water and 2.0 gpm/ton [0.036 L/s/kW] condenser water.

Energy Consumption, kW

Figure 20. System summary at full load

 

300

 

 

 

250

 

 

 

200

 

 

 

150

 

 

 

100

 

 

 

50

 

 

 

0

 

 

 

2.4/3.0

1.5/3.0

2.4/2.0

1.5/2.0

Chilled/Condenser Water Flows, gpm/ton

 

Manual background Tower

Condenser Water Pumps

Manual background Chilled Water Pump

Manual background Chiller (100% Load)

It becomes clear that flow rates can affect full-load system power (Figure 20). Even though the chiller requires more power in the low-flow system, the power reductions experienced by the pumps and cooling tower result in an overall savings for the system.

What happens at part-load conditions? Figure 21 shows the part-load performance based on the following assumptions:

The chilled-water pump includes a variable-frequency drive.

The condenser-water pump remains at constant power.

The cooling tower is controlled to produce water temperatures lower than design.

32

Chiller System Design and Control

SYS-APM001-EN

Page 38
Image 38
Trane SYS-APM001-EN manual System Design Options, The total system power is now as follows