System Configurations

Experience with actual VPF plants indicates that a minimum evaporator-flow limit of 60 percent for packaged chillers and 40 percent or less for configured chillers work well.

Chiller manufacturers specify minimum and maximum limits for evaporator water flow. Their objective?

To promote good heat transfer and stable control (minimum flow limit)

To deter vibration and tube erosion (maximum flow limit)

In the past, the typical range for water velocity in a chiller was 3 to 11 feet per second. Today, manufacturer-conducted testing shows that specific chillers may accommodate evaporator flow rates as low as 1.5 feet per second, depending on tube type. This is good news for VPF systems because it extends the chiller’s ability to operate effectively without the addition of bypass flow.

The minimum flow limit for a chiller can be lowered by selecting an evaporator with more passes (a common option for machines with cooling capacities of 150 tons or more). Granted, more passes may require a higher evaporator pressure drop and more pumping power (Table 13). However, as the system flow rate decreases, the evaporator pressure drop also decreases by approximately the square of the flow rate reduction. Therefore, the pump requires less extra power to work against the pressure drop as the system flow rate drops below the design value.

The other benefit of the added pass is better turndown with a wider evaporator ΔT, which starts at a lower design flow rate for the same cooling capacity. In the case of the two-pass chiller, when using a 15° ΔT, the chiller invoked minimum flow prior to reaching the 50 percent system flow rate. This could cause a more complicated transition from one to two chillers, as discussed in the sections on “Managing transient water flows” on page 59 and “Chiller sequencing in VPF systems” on page 63. The other issue is that more pumping energy will be used in the system that requires bypassed flow more of the time.

Table 13. Effect of number of passes on minimum evaporator flow and pressure drop at reduced flow with packaged chillers1

 

Design

Evap. pressure

Evap. pressure

Evaporator pressure

Minimum flow

Evaporator pressure

 

flow rate

drop at design

drop at 80%

drop at 50% flow rate,

rate, gpm [L/s]

drop at minimum

 

gpm [L/s]

flow, ft.water

flow rate,

ft. water [kPa]

 

flow rate, ft. water

 

 

[kPa]

ft.water [kPa]

 

 

[kPa]

 

 

 

 

 

 

 

2 pass

180 [11.4]

13.7 [40.9]

9.0 [26.9]

3.5 [10.5]

77 [4.9]

2.6 [7.8]

 

 

 

 

 

 

 

3 pass

180 [11.4]

42.6 [127.3]

28.7 [85.8]

11.9 [35.6]

52 [3.3]

4.0 [12.0]

 

 

 

 

 

 

 

2 pass

113 [7.4]

5.6 [16.7]

3.5 [10.5]

flow too low, use min.

77 [4.9]

2.5 [7.5]

(15° ΔT)

 

 

 

2.5 [7.5]

 

 

 

 

 

 

 

 

 

3 pass

116 [7.3]

19.6 [58.6]

12.8 [38.3]

5.0 [14.9]

52 [3.3]

4.0 [12.0]

(15° ΔT)

 

 

 

 

 

 

1 Chillers may have slight differences in capacity, depending on which variable (flow, capacity, or ΔT) is allowed to adjust.

58

Chiller System Design and Control

SYS-APM001-EN

Page 64
Image 64
Trane SYS-APM001-EN manual Flow, ft.water Flow rate

SYS-APM001-EN specifications

The Trane SYS-APM001-EN is an advanced control system designed for HVAC (Heating, Ventilation, and Air Conditioning) applications, specifically tailored to enhance energy efficiency and system performance. This comprehensive solution integrates cutting-edge technologies to optimize climate control in commercial and industrial environments.

One of the main features of the SYS-APM001-EN is its intuitive user interface. The system is equipped with a large, easy-to-read display that provides real-time data on system performance, energy usage, and environmental conditions. This user-friendly interface makes it simple for operators to monitor and adjust settings, ensuring optimal comfort levels and efficient energy consumption.

Another key characteristic of the SYS-APM001-EN is its advanced data analytics capabilities. The system collects and analyzes data from various sensors throughout the building, providing insights into occupancy patterns, equipment performance, and energy consumption trends. This data-driven approach allows facility managers to make informed decisions about system adjustments, predictive maintenance, and energy savings.

The SYS-APM001-EN also boasts robust integration capabilities. It can seamlessly connect with a variety of building management systems (BMS) and other third-party devices. This interoperability enables a cohesive operational ecosystem where HVAC systems can communicate and cooperate with lighting, security, and fire safety systems, enhancing overall building efficiency.

Energy efficiency is a hallmark of the SYS-APM001-EN, as it implements sophisticated algorithms to optimize system operation. These algorithms adjust equipment performance in real-time based on current conditions, thereby reducing energy waste and lowering operational costs. The system is designed to support multiple energy-saving strategies, including demand-controlled ventilation and optimal start/stop scheduling.

Additionally, the SYS-APM001-EN is built with scalability in mind, accommodating facilities of various sizes and configurations. Whether it’s a small office building or a large industrial complex, the system can be tailored to meet specific needs, ensuring that HVAC performance aligns with operational goals.

In conclusion, the Trane SYS-APM001-EN is an innovative HVAC control solution that emphasizes user experience, data-driven decision-making, and energy efficiency. With its advanced features and technologies, it is an essential tool for optimizing building performance and enhancing occupant comfort while reducing environmental impact.