System Configurations

Small packaged chillers typically offer less design flexibility than larger machines. It may not be possible to select a small packaged chiller with a minimum flow rate of less than 60 percent of the design system flow… but don’t let this deter you from designing a VPF plant that includes small packaged chillers. Remember, pump power drops with the cube of the reduction in flow, so even a modest 20 percent decrease in flow results in a 50 percent pump energy reduction. A 40 percent flow reduction yields an 80 percent pump energy reduction. The key to making variable flow with limited flow turndown work properly is devising a plant layout and sequencing strategy that accommodates the chiller’s minimum evaporator-flow limit.

Managing transient water flows

The second requirement of the selected chillers is proper control during “transient flows.” This situation refers to the hydraulic effects caused by an isolation valve when it opens (before the associated chiller starts) or closes (after the chiller stops). To illustrate what happens, let’s look at an example.

Assume that the two-chiller VPF system in Figure 37 is designed for a 16°F [8.9°C] ΔT and that it delivers 40°F [4.4°C] chilled water. The temperature of the return water remains relatively constant at 56°F [13.3°C], provided that the coils and two-way valves function properly. Only Chiller 1 operates when the cooling load is low; the isolation valve for Chiller 2 remains closed.

As the cooling load increases, the pump controller increases the rate of chilled water flow through the system. Chiller 2 starts when Chiller 1 can no longer produce 40°F [4.4°C] water. Opening the isolation valve for Chiller 2 almost instantly reduces the flow rate through Chiller 1 by half (Table 14), which effectively doubles the ΔT. Chiller 1’s controller will unload the machine as quickly as possible, but in the interim, it will attempt to produce a 32°F ΔT [0°C] and cool the water to 24°F [-4.4°C]. If the chiller cannot unload quickly enough, built-in fail-safes should stop and lock out the chiller before damage occurs… but at the expense of satisfying the cooling load. The system can be designed and operated to keep this scenario from occurring. This information is provided in the following sections.

Table 14. Flow-rate changes that result from isolation-valve operation

 

Number of operating chillers

 

 

 

 

 

 

 

 

1

2

3

4

5

 

 

 

 

 

 

Flow-rate reduction when an isolation valve

50%

33%

25%

20%

17%

opens*

 

 

 

 

 

*Flow-rate reduction is expressed as a percentage of the actual chilled water flow rate prior to transition:

%flow-rate reduction = 1– number of chillers operating number of chillers operating +1

Select for the greatest tolerance to large changes in flow rate. The objective

is to simplify system control by minimizing the need for “supplemental” demand limiting or valve control as chillers come online. Chillers that are well-suited for variable primary flow can tolerate and respond to rapid flow-

SYS-APM001-EN

Chiller System Design and Control

59

Page 65
Image 65
Trane SYS-APM001-EN manual Managing transient water flows, Flow-rate changes that result from isolation-valve operation

SYS-APM001-EN specifications

The Trane SYS-APM001-EN is an advanced control system designed for HVAC (Heating, Ventilation, and Air Conditioning) applications, specifically tailored to enhance energy efficiency and system performance. This comprehensive solution integrates cutting-edge technologies to optimize climate control in commercial and industrial environments.

One of the main features of the SYS-APM001-EN is its intuitive user interface. The system is equipped with a large, easy-to-read display that provides real-time data on system performance, energy usage, and environmental conditions. This user-friendly interface makes it simple for operators to monitor and adjust settings, ensuring optimal comfort levels and efficient energy consumption.

Another key characteristic of the SYS-APM001-EN is its advanced data analytics capabilities. The system collects and analyzes data from various sensors throughout the building, providing insights into occupancy patterns, equipment performance, and energy consumption trends. This data-driven approach allows facility managers to make informed decisions about system adjustments, predictive maintenance, and energy savings.

The SYS-APM001-EN also boasts robust integration capabilities. It can seamlessly connect with a variety of building management systems (BMS) and other third-party devices. This interoperability enables a cohesive operational ecosystem where HVAC systems can communicate and cooperate with lighting, security, and fire safety systems, enhancing overall building efficiency.

Energy efficiency is a hallmark of the SYS-APM001-EN, as it implements sophisticated algorithms to optimize system operation. These algorithms adjust equipment performance in real-time based on current conditions, thereby reducing energy waste and lowering operational costs. The system is designed to support multiple energy-saving strategies, including demand-controlled ventilation and optimal start/stop scheduling.

Additionally, the SYS-APM001-EN is built with scalability in mind, accommodating facilities of various sizes and configurations. Whether it’s a small office building or a large industrial complex, the system can be tailored to meet specific needs, ensuring that HVAC performance aligns with operational goals.

In conclusion, the Trane SYS-APM001-EN is an innovative HVAC control solution that emphasizes user experience, data-driven decision-making, and energy efficiency. With its advanced features and technologies, it is an essential tool for optimizing building performance and enhancing occupant comfort while reducing environmental impact.