Applications Engineering Manual
Chiller System Design and Control
SYS-APM001-EN
Page
Susanna Hanson, applications engineer
Mick Schwedler, applications manager
Beth Bakkum, information designer
Chiller System Design and Control
Preface
2009 Trane All rights reserved
Chiller System Design and Control
SYS-APM001-EN
Contents
Failure Recovery
Chilled-Water System Control
Condenser-Water System Control
System Controls
Primary System Components
Chiller
Primary System Components
Chiller evaporator
Figure 1. Typical vapor-compression chiller
Figure 2. Flooded evaporator cut-away
Effect of chilled-water temperature
Primary System Components
Effect of chilled-water flow rate and variation
Figure 3. Direct-expansion evaporator cut-away
Water-cooled condenser
Effect of condenser-water temperature
Primary System Components
Effect of condenser-water flow rate
Air-cooled condenser
Air-cooled versus water-cooled condensers
Maintenance
Primary System Components
Low-ambient operation
Primary System Components
Energy efficiency
Loads
Primary System Components
1212 Midnight midnight
dry bulb wetWetbulbBulb
Three-way valve load control
Two-way valve load control
Primary System Components
Heat transferred from the loads can be controlled in a number of ways
Variable-speed pump load control
Face-and-bypass dampers
Primary System Components
Figure 6. Two-way valve
Chilled-Water Distribution System
Chilled-water pump
Primary System Components
Figure 8. Uncontrolled water flow with bypass damper
Distribution piping
Primary System Components
Pump per chiller
Manifolded pumps
Pumping arrangements
Primary System Components
Constant flow system
Figure 12. Constant flow system
Condenser-Water System
Cooling tower
Primary System Components
Primary-secondary system
Condenser-water pumping arrangements
Primary System Components
Effect of load on cooling tower performance
Effect of ambient conditions on cooling tower performance
Primary System Components
Unit-Level Controls
Chiller control
Centrifugal chiller capacity control
Primary System Components
Figure 16. Centrifugal chiller with AFD
The availability of cooler condenser water condenser-water reset
Primary System Components
Application Considerations
Small Chilled-Water Systems 1-2 chillers
Variable flow
Application Considerations Constant flow
Condensing method
Application Considerations
Number of chillers
Parallel or series
Part load system operation
Mid-Sized Chilled-Water Systems 3-5 Chillers
Managing control complexity
Preferential vs. equalized loading and run-time
Figure 18. Mid-sized chilled-water system schematic
Figure 19. Large chilled-water system schematic
Large Chilled-Water Systems 6+ Chillers, District Cooling
Application Considerations
Power
Pipe size
Water
Creating one centralized chilled-water system takes significant foresight, initial investment, and building development with a multi-year master plan. If the initial plant is built to accommodate many future buildings or loads, the early challenge is operating the system efficiently with much lower loads than it will experience when the project is complete. The system may need to blend parallel and series configurations “Series-Counterflow Application” on page 77 to accommodate the wide range of loads the plant experiences during phased construction
Chiller performance testing
Limitations of field performance testing
Chiller Plant System Performance
Controls
Application Considerations
Guidelines for system efficiency monitoring
Guideline 22 includes a discussion of
Application Considerations
Energy and economic analysis of alternatives
1 Full year analysis
System Design Options
Selecting Chilled- and Condenser-Water Temperatures and Flow Rates
Guidance for Chilled- and Condenser-Water Flow Rates
Standard rating temperatures
Chilled-Water Temperatures
System Design Options
Condenser-Water Temperatures
Chilled- and Condenser-Water Flow Rates
Standard rating flow conditions
System Design Options
System Design Options Selecting flow rates
System Design Options
DP2/DP1 = Flow2/Flow11.85
The total system power is now as follows
System Design Options
Coil response to decreased entering water temperature
Example of coil reselection at colder temperature/reduced flow rate
System Design Options
Figure 21. Chilled water system performance at part load
Cooling-tower options with low flow
System Design Options
Smaller tower
Fluid ΔT, F C
System Design Options
ΔT1 = 94.2 - 78 = 16.2F or 34.6 - 25.6 = 9.0C
ΔT2 = 99.1 - 78 = 21.1F or 37.3 - 25.6 = 11.7C
Same tower, smaller approach
System Design Options
Same tower, larger chiller
Retrofit opportunities
System Design Options
range
Reselected tower for 50% more heat rejection with 15F 8.3C
Cost Implications
System Design Options
Misconception 1-Low flow is only good for long piping runs
Misconceptions about Low-Flow Rates
System Design Options
System Design Options
Consumption
Energy
System
System Design Options
Demirchian and Maragareci12, Eley13, and Schwedler and Nordeen11 independently showed that system energy consumption can be reduced by reducing flow rates. It is interesting to note that in the systems studied, three different chiller manufacturer’s chillers were examined, yet the energy savings only varied from 2.0 to 6.5 percent. In all cases, regardless of which manufacturer’s chillers were used, the system energy consumption was reduced. In addition, Demirchian and Maragareci12, and Schwedler and Nordeen11 also noted reduced first costs
System Configurations
Parallel Chillers
System Configurations
System Configurations
Series Chillers
Figure 27. Series chillers
Hydraulic decoupling
Primary-Secondary Decoupled Systems
System Configurations
System Configurations
bypass piping no-flow static head from the building water column, and
System Configurations Production
Figure 29. Production loop
System Configurations Distribution
Distribution-loop benefits of decoupled system arrangement
System Configurations
Pumping arrangements
Common
Campus
Decoupled system-principle of operation
System Configurations
Figure 34. Decoupled system supply tee
Flow-based control
System Configurations
Temperature-sensing
Figure 35. Temperature-sensing
System Configurations Chiller sequencing in decoupled systems
Multiple chilled-water plants on a distribution loop
Adding a chiller
Subtracting a chiller
Pump control in a double-ended decoupled system
System Configurations
Figure 36. Double-ended decoupled system
System Configurations
Chiller sequencing in a double-ended decoupled system
Variable-Primary-Flow Systems
Other plant designs
System Configurations
Figure 37. Variable-primary-flow system
System Configurations
Advantages of variable primary flow
Operational savings of VPF designs
Chiller selection requirements
System Configurations
Evaporator flow limits
Dispelling a common misconception
System Configurations
To promote good heat transfer and stable control minimum flow limit
System Configurations
Flow-rate reduction when an isolation valve
Managing transient water flows
Number of operating chillers
System Configurations
System Configurations
System design and control requirements
These descriptions should include control sequences for
Accurate flow measurement
System Configurations
Bypass locations
System Configurations
Chiller sequencing in VPF systems
Bypass flow control
System Configurations
Adding a chiller in a VPF system
Subtracting a chiller in a VPF system
System Configurations
Sequencing based on load
Other VPF control considerations
System Configurations
Select slow-acting valves to control the airside coils
Use multiple air handlers, and stagger their start/stop times
Plant configuration
System Configurations
Consider a series arrangement for small VPF applications
Assess the economic feasibility of VPF for single-chiller plants
Guidelines for a successful VPF system
System Configurations
Moderate “low ΔT syndrome” by manifolding the chilled water pumps
Chiller selection
System Configurations
Plant configuration
Bypass flow
Chiller sequencing
Heat Recovery
Chilled-Water System Variations
Condenser “Free Cooling” or Water Economizer
Plate-and-frame heat exchanger
Refrigerant migration
Chilled-Water System Variations
Figure 41. Refrigerant migration chiller in compression cooling mode
Well, river, or lake water
Figure 42. Refrigerant migration chiller in free-cooling mode
Chilled-Water System Variations
Figure 43. Water economizer piped in parallel with chillers
Preferential Loading
Preferential loading - parallel arrangement
Chilled-Water System Variations
Figure 44. Parallel preferential loading arrangement
Preferential loading - sidestream arrangement
Chilled-Water System Variations
Sidestream plate-and-frame heat exchanger
Figure 45. Sidestream preferential loading arrangement
Sidestream with alternative fuels or absorption
Recovery
Production
Preferential loading - series arrangement
Chilled-Water System Variations
Sidestream system control
Figure 47. Preferential loading - series arrangement
Series-Counterflow Application
Series-series counterflow
Chilled-Water System Variations
Figure 48. Series-counterflow arrangement
Unequal Chiller Sizing
Chilled-Water System Variations
Figure 50. Series arrangement of evaporators and condensers
Evaporators
System Issues and Challenges
Low ΔT Syndrome
Amount of Fluid in the Loop
Required Volume = Flow Rate × Loop Time
System Issues and Challenges
Chiller response to changing conditions
System response to changing conditions
Example
Contingency
Minimum capacity required
Type and size of chiller
System Issues and Challenges
System Issues and Challenges Location of equipment
Alternative Energy Sources
Water and electrical connections
Ancillary equipment
Plant Expansion
Alternative fuel
Thermal storage
System Issues and Challenges
Retrofit Opportunities
Applications Outside the Chiller’s Range
Flow rate out of range
System Issues and Challenges
Precise temperature control
System Issues and Challenges Temperatures out of range
Figure 52. Temperatures out of range for equipment
System Issues and Challenges
Figure 53. Precise temperature control, multiple chillers
Chiller System Design and Control
SYS-APM001-EN
Chilled water reset-raising and lowering
System Controls
Chilled-Water System Control
Chilled-water pump control
Number of chillers to operate
System Controls
Critical valve reset pump pressure optimization
Condenser-Water System Control
Minimum refrigerant pressure differential
System Controls
Table 17. VFDs and centrifugal chillers performance at 90% load
System Controls
Condenser-water temperature control
Cooling-tower-fan control
Chiller-tower energy balance
System Controls
Figure 54. Chiller-tower energy consumption
System Controls Variable condenser water flow
Chiller-tower-pump balance
System Controls
Decoupled condenser-water system
These three energy consumers must be balanced to minimize overall energy use. This makes varying condenser water flow complex, but the strategy below has been implemented on projects
System Controls
Cooling Tower Fan Inverter Cooling Tower Water Sump Tower Water
Recirculation Pump CDWP-2 Inverter Chiller CDWP-1 Inverter Chiller
Figure 56. Decoupled condenser-water system
Figure 57. Failure recovery
Failure Recovery
System Controls
Conclusion
condenser water, leaving. See cooling water
Glossary
cooling tower water. See cooling water
Glossary
pumps system
Glossary
tower water. See cooling water
References
Plant.” IDEA 88th Annual Conference Proceedings 1997
References
Engineering July
ASHRAE/IESNA Standard 90.1-2007 Energy Standard for Buildings
Except Low-Rise Residential Buildings. ASHRAE and IESNA
References
32 Trane Applications Engineering Group. “Thermal Storage - Understanding the Choices.” Ice Storage Systems, Engineered Systems Clinics. Trane, 1991. ISS-CLC-2
Index
Index
Index
Index
Page
Trane
Literature Order Number
SYS-APM001-EN
Date