Trane SYS-APM001-EN manual Plant configuration, System Configurations

Models: SYS-APM001-EN

1 114
Download 114 pages 32.43 Kb
Page 73
Image 73
Plant configuration

System Configurations

For more information, refer to the Trane Engineers Newsletter, Don’t Overlook Optimization Opportunities in ’Small’ Chilled Water Systems” (ADM-APN009- EN).

Plant configuration

Consider a series arrangement for small VPF applications.

When the plant consists of only two chillers and expansion is unlikely, you can simplify control by piping the evaporators in series. Doing so avoids flow transitions because the water always flows through both chillers. The series arrangement requires careful selection because the pump must be sized for the pressure drop through both chillers. However, the extra pressure quickly decreases (by roughly the square of the flow rate) as the flow rate slows. For example, at 80 percent of design flow, the evaporator pressure drop is only 64 percent of design. Given this operating characteristic, a VPF design may permit a slightly higher system pressure drop than a comparable primary– secondary system without a noticeable penalty in operating cost. “Series Chillers” on page 44 discussed these arrangements in greater detail.19

Note: To further reduce the system ΔP, lower the required rate of chilled-water flow through the system by increasing the temperature difference between the supply and return. Plants that supply 40°F [4.4°C] chilled water based on a ΔT of 16°F [8.9°C] or more are increasingly common.

Assess the economic feasibility of VPF for single-chiller plants.

Although most VPF applications consist of two or more chillers, variable primary flow also offers potential operating-cost savings in a new or existing single-chiller plant. Instead of a bypass line and flow-sensing devices, minimum flow through the chiller can be maintained by three-way valves. (Use enough three-way valves to assure that the minimum evaporator-flow rate of the chiller is always satisfied.) This simple approach will reduce pumping costs while providing the chiller with enough chilled water.

To quantify the savings potential of variable versus constant primary flow in a single-chiller plant, we examined a two-story office building in St. Louis, Missouri. The HVAC system includes a 50-ton scroll chiller and a 5-hp chilled water pump. Figure 39 illustrates the results of our analysis. Although the absolute savings are not large, variable primary flow did reduce the cost of operating the chilled water system by more than 6 percent … enough to warrant further investigation. The difference in installed costs is a variable- speed drive, a differential pressure sensor, and a pump controller.

SYS-APM001-EN

Chiller System Design and Control

67

Page 73
Image 73
Trane SYS-APM001-EN Plant configuration, System Configurations, Consider a series arrangement for small VPF applications