System Controls

separate wetting (recirculation) pump provides a constant flow of water through the tower. This is a low-energy pump, as very little lift is required.

Dedicated, variable-flow condenser pumps (CDWP-1 and CDWP-2) permit a reduction in the pumping energy whenever the temperature of condenser water results in an unproductive reduction of condenser refrigerant pressure. While the number of dedicated pumps may seem complicated at first, remember the number of valves and controls that are eliminated.

Figure 56. Decoupled condenser-water system

Cooling Tower Fan (Inverter)

Cooling

Tower

Water Sump

Tower Water

Recirculation

Pump

CDWP-2

(Inverter) Cooling Tower Fan (Inverter)RecirculationManual background Chiller 2

CDWP-1

(Inverter)

Chiller 1

94

Chiller System Design and Control

SYS-APM001-EN

Page 100