F3200 Installation & Programming Manual

Document No: LT0122

Programming System Configuration

 

OPERANDS TYPE 1 (CONTINUED)

Notes:

1.When entering numbers, leading zeros need not be entered.

2.Alarm and Fault refer to the latched status for a latching zone and the current status for a non-latching zone.

3.None of these zone tokens are affected by the programming of a zone as MAF mapped, non-MAF or status only.

4.The circuit input refers to the "debounced" circuit input prior to the 2.3 second filter and zone "latch". That is, it takes 80-240 milliseconds to change state, is a non- latching condition, and is independent of zone programming or isolation (including the automatic isolation in Auto-Reset mode). Refer also to Section 7.4.10.

WARNING

The zone operands ZnD (detector operated) and ZnM (MCP operated) can return a value which is not the true condition of the circuit input in a number of situations as follows:

1.During zone reset (other than AVF reset or Auto-Reset mode reset) the ZnD and ZnM operands will be the value that existed at the start of the reset. This includes the 2 second post reset delay, a total of 7 seconds. After this they will be the current state of the circuit input. This is true only for V1.10 software onwards. For earlier V1.0X versions of software ZnD and ZnM are both FALSE for the duration of the reset.

2.During AVF reset and Auto-Reset mode reset the state of the circuit input is forced to be B1 (Band 1) during the actual 5 second/15 second circuit reset and at the end of this period may temporarily be any of the values B1, B2, B3, B4 or B5 until the circuit and detectors power up again.

Thus the operands ZnD and ZnM may be true during these times depending on the programming of the circuit.

Band B2 always maps to detector operated/alarm. Bands B1 and B3 may be programmed to map to any of MCP operated (instant alarm), Detector Operated (alarm), fault and normal. During AVF Reset and Auto-Reset mode reset the tokens ZnD and ZnM will follow the state of the circuit. E.g. If B1 is programmed as instant alarm then ZnM will return true during the reset when the state of the circuit is B1.

3.During System Test and Auto-Test circuit alarm testing, any circuit which has an alarm test applied to it will be in band B3. Operands ZnD and ZnM will return true or false according to the programming of band B3.

Note that not all zones are tested by System Test and Auto-Test. Zones which are not tested include:

1.Isolated zones.

2.Zones which are already in alarm or fault at the start of the test.

3.Status only zones.

4.Zones where the current input state is B1 and B1 is programmed to be normal.

4.During zone alarm test the ZnD operand will return true if the test operates correctly.

Page 7-16

5 July 2001

Issue 2.7

Page 118
Image 118
Tyco F3200 manual Operands Type

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.