12.8INSTALLATION : NZ DISPLAY EXTENDER BOARD

&BRIGADE DISPLAYS

12.8.1GENERAL

An NDU is not normally used as a brigade connection point. If an NDU is used as a brigade connection point then, in general, a separate display panel must be provided if there needs to be zone alarm indication to the attending Fire Brigade staff. The common MAF status display is provided by mounting an NZ Display Extender Board (PA0499 or PA0762), in the NDU cabinet and wiring to display in a separate cabinet in one of three different ways as shown in Fig 12.8.1, 12.8.2, and 12.8.3.

Sixteen-zone display boards are not normally connected to an NDU, but the three diagrams show how they can be connected if necessary. An NDU allows a maximum of four 16-zone display boards and each individual LED (48 LEDs per board) must be controlled using output logic which is generally too cumbersome for normal use.

The second cabinet is necessary because the LEDs mounted inside the NDU cabinet do not meet the requirements of NZ4512 with regard to visibility and viewing access. An NLDU (Network LED Display Unit), can often be used to more conveniently drive 16-zone display boards and show individual zone information as part of the brigade mimic display.

Any Ancillary Control Zone indicators on this external display must be coloured differently or be segregated from the zone alarm and common indicators, and be clearly labelled.

There are several methods for providing a separate display panel. Two approaches are detailed below.

NOTE 1: The information provided here is very similar to the information in the RDU

installation manual LT0148 which may be useful to refer to.

NOTE 2: As stated above, 16 zone display boards are not normally connected to an NDU, nevertheless, the following sections describe how to do it if necessary. If an NLDU is used to drive 16 zone display boards, then the NLDU user manual LT0188 must also be referred to.

12.8.2MIMIC DISPLAY

A mimic display uses the mimic outputs from the NDU’s internal 16 Zone LED Indicator Boards to drive alarm LEDs in an external display. Each group of 16 zone alarms and the common indicators are extended in a separate 26 way FRC to the external display.

The number of FRCs between the NDU and the external display limit the practical separation distance. Since the cabling is not supervised in any way, the Fire Service or approving authority may place restrictions on this distance. The cable must be well protected mechanically by conduit, trunking or equivalent.

These parts are available for constructing displays of this type:

FP0475 FP,16 ZONE LED DISPLAY EXTENDER KIT (C/W LOOM)

FZ3031 16 ZONE LED DISPLAY EXTENDER KIT, RHS POSITION

LM0044 LOOM, DISPLAY EXTENDER FRC,2M,26 WAY

LM0045 LOOM, DISPLAY EXTENDER FRC,5M,26 WAY (Longer and 3-way looms can be made to special order)

Page 12-10

5 July 2001

Issue 2.7

Page 246
Image 246
Tyco F3200 manual Installation NZ Display Extender Board Brigade Displays, Mimic Display

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.