6.1INTRODUCTION

6.1.1GENERAL

The F3200 has two main levels of programming. The first level is accessible to the Operator (via the keypad) and does not require entry of an access code. It allows the setting of parameters, such as time and date, which do not affect the basic structure of the system.

The second level allows entering of data into the database to configure the operation of the FIP. It is accessible only by fitting the WRITE ENABLE link on the Controller and entering an access code on the keypad. When this level has been accessed, Alarm and other I/O processing is stopped.

The FIP can be programmed from the keypad and the database can be saved to a computer, and restored from a computer, in binary format. (Currently, the database can not be configured off line on a computer. It can only be configured from the FIP keypad).

It is recommended that, for each FIP, configuration sheets specifying Text and all parameters, be filled out before programming commences. Some suggested master sheets are included in Appendix B. A set of completed sheets should be kept in the contract file.

NOTES

1.When filling out configuration sheets it is only necessary to record any non-default parameters.

2.It is necessary to install and configure the modules before the other programming, such as text entry, is performed.

The recommended order of configuration and programming is shown in Section 6.1.4.

6.1.2MENU STRUCTURE & PARAMETER ENTRY

The Programming menu structure of the F3200 takes the form of an inverted tree, with a display screen for every branch. Each screen shows an item with parameters to be changed, a prompt, or a menu of options.

Options are normally preceded by numbers, and the desired choice is made by pressing the appropriate digit on the numeric keypad (1-9).

The general method of programming is to step down the branches of the tree by selecting options until the sub-level which contains the items to be programmed (e.g. Configure Zones) is reached. Items (e.g. Zone 1, Zone 2, etc) can be stepped through by use of the "NEXT" and "PREV" keys.

When an item is selected, the attributes (e.g. MAF Mapping) are selected by use of the horizontal cursors (! "). For each attribute selected the options are displayed. Options (e.g. N for non-mapped, M for mapped) are selected by use of the vertical cursor (#), or, in cases where there are more than two choices, pressing the digit associated with the desired option.

When all the desired attributes for an item have been selected they are saved into the database (where applicable) by pressing "ACK".

The "CLEAR ESC" (Escape) key is used to return up levels in the menu tree. To get from one branch of the tree to another branch of the tree, generally "CLEAR ESC" must be repeatedly pushed until the menu option gives the choice of the two branches.

Page 6-2

5 July 2001

Issue 2.7

Page 68
Image 68
Tyco F3200 manual 1INTRODUCTION, Menu Structure & Parameter Entry

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.