Document No: LT0122

F3200 Installation & Programming Manual

 

Applications

6 TERMINAL ISOLATED REPEATER (CONTINUED)

Notes

1.Circuit lengths quoted are from the isolator to the EOL. An extra 50 Ohms of cable from the FIP to the isolator is also allowed (1.5km of 1.0mm², 1.1km of 0.75mm²). The length quoted is the maximum for the corresponding quantity of detectors.

2.Cable resistance shown is for the circuit, ie. both cables in the pair. The value of 34Ω per km (return) is used for 1 mm².

3.The maximum resistances shown for the fire wire circuits must include both cable and fire wire (see Table 9.4.2 and associated note 2).

4.The letter in ( ) after the cable length, and the value in ( ) under the cable length specify which parameter out of capacitance (C), inductance (L) and resistance (R) provides the limitation, and what the maximum value is.

5.The (M) after a detector quantity indicates the maximum quantity allowed per circuit.

6.The maximum allowable detector quiescent (or 2 second switch on) current is 3.5mA (only relevant to R24BEx).

7.The C23BEx detector (old type) would be compatible but has not been tested in this configuration.

9.4.3.34 TERMINAL ISOLATED REPEATER WITH ZONE ADAPTOR UNIT

ZAU401

With the addition of the ZAU401 Zone Adaptor Unit (PA0838), lower-cost 4-terminal isolating repeaters can be used with the F3200 panel.

The ZAU401 can be thought of as a single zone circuit module that can be added to a panel to make it compatible with a wider range of detectors – in particular when using IS repeaters.

The ZAU401 can support up to 2mA of quiescent detector current and uses a 3k9 5% EOL resistor.

Wiring of the ZAU401 and the isolating repeater to the panel is shown in Figure 9.4.3.3. Note that only one ZAU401 can be connected to each of the panel’s zone circuits.

The following 4-terminal isolating repeaters can be used to connect the ZAU401 to an IS detection circuit. (Note that dual channel repeaters have two separate repeaters, and can connect two circuits with two ZAU401s).

Pepperl & Fuchs

KHD0-ICS/Ex 1.51

(single channel)

Pepperl & Fuchs

KHD0-ICS/Ex 2.51

(dual channel)

Pepperl & Fuchs

KFD0-CS-Ex 1.51P

(single channel)

Pepperl & Fuchs

KFD0-CS-Ex 2.51P

(dual channel)

Measurement Technology Ltd

MTL5061 (dual channel)

Issue 2.7

5 July 2001

Page 9-27

Page 197
Image 197
Tyco F3200 manual 3.3 4 Terminal Isolated Repeater with Zone Adaptor Unit, ZAU401

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.