F3200 Installation & Programming Manual

 

New Zealand Operation

12.7.1THE SID LIST

Normally, all other panels on the network are entered into the SID list of the NDU, with 8 options able to be set for each panel.

If the NDU is the brigade connection point of the system, then probably all 8 options will be enabled for every SID in the list. When the option “use MAF relay data” is enabled for a SID, the NDU will signal the brigade for faults and alarms received from that SID.

Even if the NDU is not the main brigade connection point of the system, it may still need to have the “use MAF relay data” option enabled for SIDs in its SID list for the following reasons.

1.To signal alarm and defect on the New Zealand Display Extender board LEDs and outputs when an alarm or defect occurs on another panel.

2.To control the NDU bell relay, if any, for an alarm or trial evac condition on another panel.

3.To display the network bells silence state by flashing the bells isolate LED.

The most situations, the NDU should have the “use MAF totals” option enabled for each panel in the SID list that it has “use MAF relay data” enabled.

The “RX FFCIF” option should be enabled in the SID list for any panel that the NDU is to display FFCIF alarms for.

12.7.2NETWORK MAF CONFIGURATION Section 11.5 of this manual describes these options:

1.“Receive net bells control”

This option should be enabled if the NDU bell relay is to operate when a MAF alarm or Trial Evac on another panel is to operate the bell relay at this panel.

2.“Send bell isolate as net silence”

This option, if enabled, means that a local bells isolate state is sent onto the network as network bells silence and also that a defect is signalled for bells isolate. If this option is disabled, a defect is not signalled for bells isolate. When the local silence alarms keyswitch (if any) is operated, a network bells silence state is always sent on the network regardless of the “send bell isolate as net silence” parameter.

3.“Allow receive net bells silence”

This option must be enabled if the NDU is to keep its alarm bells (if any) off in response to a network silence state sent from another panel.

12.7.3NETWORK FFCIF CONFIGURATION

Section 11.7 of this manual describes the options for this. The Tx alarms option should be enabled if the NDU should send an FFCIF alarm on the network when its local MCP zone goes into alarm.

Issue 2.7

5 July 2001

Page 12-9

Page 245
Image 245
Tyco F3200 manual SID List, Network Ffcif Configuration

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.