F3200 Installation & Programming Manual

Document No: LT0122

Network Programming

 

11.5 NETWORK MAF CONFIGURATION

As described in section 11.2.2, a panel will transmits its MAF status and totals onto the network for use by other panels, if programmed to. If both the “Refresh Tx Time” and the “Max COS rate” listed below are zero then this panel will not transmit MAF status.

The MAF status and totals are transmitted at regular intervals, defined by the 'Refresh TX time'. If a change of MAF Status occurs the new MAF status will be transmitted immediately as long as the minimum time specified by 'Max Cos TX Rate' has elapsed since the last transmission of MAF status.

If individual brigade signals are required per panel on the network, Network Variables can be used to transfer the status and to control the relays.

The < and > keys allow movement between two menus named NetMAF1 and NetMAF2.

11.5.1OPTIONS UNDER NETMAF1

F3200 V2.07 or later software allows the following options to be set to zero. If both are zero, the panel will never send MAF status onto the network.

1. Refresh TX time : (0-250)

A value in seconds which specifies the rate at which a refresh of the network MAF status/totals of this SID should be transmitted onto the network.

2. Max COS rate : (0-250)

This is a value in seconds which specifies the maximum rate at which MAF status can be transmitted into the network. If set to zero then MAF status is sent according to the Refresh Tx time and is not sent for every change of state.

11.5.2OPTIONS UNDER NETMAF2

1. Receive net bells control : (Yes/No)

If enabled, allows the local bell relay to operate when a MAF alarm occurs on another panel. The SID number of the remote panel must also be entered into the SID list of this panel and have "Use MAF relay data" enabled if a MAF alarm at the remote panel is to operate the bells at this panel.

2. Send bell isolate as net silence : (Yes/No)

If enabled will cause this panel to send a network silence state onto the network when the local bells are isolated. This can then silence the bells at any other network panel that has "Allow receive net bells silence" enabled (see Section 11.5.3) AND is programmed to use the MAF status of this panel.

11.5.3OPTIONS UNDER NETMAF3

1. Allow receive net bells silence. (Yes/No)

If enabled, allows this panel to use a network silence state received from a remote panel to keep the local bells off (providing the remote panel also appears in the SID list of this panel and has "use MAF relay data" enabled). Hence, isolating the bells at a remote panel can cause it to transmit a network silence state which is received by the local panel and will cause the bells to remain off at the local panel.

If disabled, any network silence state received from other panels is ignored.

Page 11-14

5 July 2001

Issue 2.7

Page 224
Image 224
Tyco F3200 manual Network MAF Configuration, Options Under NETMAF1, Options Under NETMAF2, Options Under NETMAF3

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.