Tyco F3200 manual Ancillary Relay Supervision

Models: F3200

1 284
Download 284 pages 12.77 Kb
Page 135
Image 135

Document No: LT0122

F3200 Installation & Programming Manual

 

Programming System Configuration

 

 

7.5

RELAY SUPERVISION

7.5.1GENERAL

The Ancillary relays (Anc1 and Anc2) and Bells relay on the MAF/PSU, and the Module relays all have the option of supervision (i.e. checking the wiring from a relay to its load to see that it is not "short" or "open" circuited).

In F3200, the supervision also includes a "confirmation" function i.e. it expects to "see" a different state after a relay has been activated. If an incorrect state is "seen" by the supervision, before or after relay activation, then it generates a "fault" condition for that relay. Supervision in the activated state can be disabled for “load” mode if it is not required, for example when the relay switches the load to 0V.

For each relay the supervision can be disabled if not required, mapped to the MAF, and made latching or non-latching. Anc 1 + 2 relays can be programmed for two different modes of supervision - door holder or load mode. All relays can also be individually made non- isolatable (stops the Operator isolating them) and non-testable.

The Relay (Supervision) menu (Option 5 on the System Configuration menu) has two options as follows: 1 Bells/Ancillary Relays; 2 Module Relays. The options for selecting relays as Isolatable, Testable and Supervise Activated state are available in V2.09 or later software.

7.5.2BELLS & ANCILLARY RELAY SUPERVISION This is option 1 in the Relay Supervision menu.

Refer to Section 3.4.2 for the electrical characteristics of the Bells and Anc1, Anc2 relay supervision.

Ancillary Relay Supervision

The options which may be entered for Anc1, 2 and Anc3 are:

Supervision enabled (E) or disabled (D).

Supervision latching (L) or non-latching (N) (i.e. the fault condition).

Fault and isolate mapped (M) or not mapped (N) to the MAF.

Supervision is load (L) or door holder (D) mode (not for ANC3).

Isolatable (yes/no)

Testable (yes/no)

Supervise Activated State (yes/no)

The default setup (by EEPROM initialise) is.

ANC 1: supervision disabled, non-latching, mapped to MAF, Door holder, isolatable, testable, activated state supervised.

ANC 2: supervision disabled, non-latching, mapped to MAF, Load mode, isolatable, testable, activated state supervised.

ANC 3: supervision disabled, non-latching, mapped to MAF, isolatable, testable, activated state supervised.

Issue 2.7

5 July 2001

Page 7-33

Page 135
Image 135
Tyco F3200 manual Ancillary Relay Supervision

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.