F3200 Installation & Programming Manual

Document No: LT0122

Programming

 

GLOBAL DATA (CONTINUED)

Country Coder (alarm signalling)

This is only required for FIPs connected to Brigades with NSW Country Coder equipment.

It allows the selection of a code of 1 to 6 pulses to be signalled on the FIP Brigade Alarm relay. These occur in a repeated sequence of 3 seconds off followed by 1 second on for each pulse, with a space of 1 second between pulses.

Select the coder option and enter the digit for the required number of pulses.

The default code (0) programs standard Alarm relay operation.

Printer setup

The printer setup menu options are:

1:Lines per page; 2:Baud Rate; 3:Print relay controls; 4:more

Option 1:lines per page, determines how often a new page/page heading is printed and option 2:baud rate allows the baud rate of the printer serial port to be selected.

Option 3 allows the enabling/disabling of the printing of relay control events (activate/deactivate).

Option 4:more gives a further menu: 1:Event printing; 2:Select print evt; 3:Select history evt

Option 1 allows event printing to be enabled or disabled. When event printing is disabled no events at all are printed and the size of the history queue is doubled.

Options 2 and 3 allow the selection of which types of events are to be printed and which type are to be logged to history. There are six different types which can be individually enabled or disabled, and these are shown as

1:Zone 2:System 3:Sys run 4:Cct 5:Pnt 6:Relay.

Numeric keys 1 to 6 are used to enable or disable each type. A 'Y' character is shown if the type is enabled and 'N' for disabled.

Zone events include zone alarm, reset, isolate etc.

System events include "system test passed", "system power up" etc, and includes all events which are not one of the other 5 types.

Sys run (system running), is for the daily "auto test passed" event (or for network systems the daily "system running" event).

Cct (circuit) and pnt (point) apply only to network systems.

Relay events include local ancillary and module relay events such as isolate, fault, operate test, and (de)activate. If relay events are enabled then local relay activate and relay deactivate events may be separately disabled (as described in the previous menu). For network systems, module relay and ancillary relay events are sent onto the network as zone events and hence the printing and history logging of them is controlled by the zone type option and not the relay event type option. However, it is possible to disable the transmission of relay activate and deactivate events onto the network - refer to section 11.8.

Page 6-26

5 July 2001

Issue 2.7

Page 92
Image 92
Tyco F3200 manual Country Coder alarm signalling, Printer setup

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.