F3200 Installation & Programming Manual

Document No: LT0122

Network Programming

 

NETWORK MAF STATUS (CONTINUED)

5.System fault state.

True if any system fault is present. When true, this will cause any panel on the network which is programmed to use the MAF data from this panel, to energise the MAF fault relay and, (if the receiving panel is an F3200 panel), to turn its buzzer on when a new fault occurs.

6.Brigade test state.

True if a brigade test has been initiated (by holding down the brigade test key for 2 seconds) AND the local MAF alarm relay, (if any), is programmed to operate for a local brigade test. When true, this will cause any panel on the network which is programmed to use the MAF data from this panel, to energise the MAF alarm relay.

7.Silence alarms state.

True if the bells are isolated and the panel is programmed to send bells isolate as network silence. When true, this will cause any panel on the network which is programmed to use the MAF data from this panel AND is programmed to allow the receiving of network bells silence, to keep the bells off. For New Zealand operation this also includes the state of the silence alarms keyswitch.

NOTE 1.

In F3200 each zone may be individually mapped to MAF, BELLS, ANC1, and ANC2. However, the mapping of a zone to BELLS, ANC1 and ANC2 has NO effect on the MAF data transmitted on the network - it effects only the local relays on that panel. Mapping a zone to bells will cause the bells to turn on at the local panel of that zone but not at a remote panel. Mapping a zone to the MAF may cause the bells to turn on at a remote panel when the zone goes into alarm. Mapping a zone to ANC1/ANC2 will cause the respective ancillary relay to turn on at the local panel of that zone but not at a remote panel.

At any F3200 panel, the MAF status and totals it is currently receiving from any other panel may be viewed by recalling net panel status ( from the base display press [RECALL] [RECALL] [3] - refer also to the F3200 operator's manual ).

F3200 output logic tokens affected by network MAF status

The output logic tokens in an F3200 panel that are affected by the MAF status received from other panels are listed below. These tokens are not affected by MAF status from another panel unless that panel is programmed into the SID list of this panel and has "use MAF relay data" option enabled (refer section 11.4.3).

NML

This token is described in Section 7.4.3.2 and is affected by any network states

 

which cause the Brigade Alarm or Brigade Fault relays to operate at this panel. This

 

includes MAF alarm, MAF fault or system fault received from a SID that this panel is

 

programmed to use the MAF status of.

 

BEL

False if the bells are locally isolated or if

 

 

[common network bells silence is true AND this panel has "receive network bells

 

SILENCE" enabled], otherwise true if

 

 

1.

Local 5 second bells test occurring.

 

 

2.

2 second ring for alarm on local zone in auto reset mode.

 

 

3.

Alarm on any local non isolated zone mapped to bells

 

 

4.

Common network maf alarm AND "receive network bells CONTROL"

 

 

enabled.

 

 

5.

Any entry in the FFCIF alarm queue and bells on for FFCIF alarm has been

 

 

enabled with programming.

 

 

Note:

For New Zealand operation, BEL will become true if the trial evac keyswitch is

 

 

operated regardless of bells isolation or silence alarms.

 

Page 11-6

5 July 2001

Issue 2.7

Page 216
Image 216
Tyco manual F3200 output logic tokens affected by network MAF status, Nml

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.