F3200 Installation & Programming Manual

Document No: LT0122

Applications

 

CIRCUITS & ZONES (CONTINUED)

Where a "Fault" contact is available, along with "Run", both can be put onto a single AZC with the NO "Fault" contact shorting the AZC and voltage band B1 programmed as "Fault" (refer to Fig 9.1.5 A). Alternatively, the NC "Fault" contact can be put in series for open circuit Fault, and the NO "Run" contact can short the AZC, with B1 programmed as "Alarm" (ZnD). (Refer to Fig 9.1.5 B). Note that in A, Fault overrides Run, and in B, Run overrides Fault. The priority in B can be reversed, but not in A.

The zone should be configured as non-latching.

If a "run" contact is used to short a Zener across the AZC (i.e. run is B2 = Alarm) and the normal state of the fan is "run", then the zone mapping to MAF should be configured as "Status Only" so that the fan "Run" state is not shown in the "Totals" or "Alarm Recalls".

 

 

 

 

┌──┐

 

NC

 

┌──┐

┌───────┬────────┬───────┤

│+

┌─────o───o──────┬───────┤

│+

RUN o FAULT o

└──┘

FAULT

o RUN

└──┘

┌┴┐

 

NO /

NO /

AZC

 

┌┴┐

 

/ NO

AZC

 

│ │2K7

o

o

 

│ │2K7

 

o

 

└┬┘

 

╒╧╕6V8

 

 

└┬┘

 

│ RUN

 

 

 

│ │OR

┌──┐

 

┌──┐

 

└┬┘560E

 

└───────┴────────┴───────┤

│-

└────────────────┴───────┤

│-

A.

 

 

 

└──┘

B.

 

 

└──┘

FIG 9.1.5

EXAMPLE OF FAN RUN & FAULT WIRING TO AZC

9.1.3RELAYS

The exact number of relays per fan control and the logic required depends on the particular building and air conditioning plant.

Typically, one relay is required per fan to switch an interposing relay in the fan control equipment, with a possible logic equation as follows:

R5 = Z15D + Z15N.Z5A i.e. ("off") or ("auto" and duct alarm) (ie. the relay turns on to turn the fan off).

Where:Relay 5 is the Fan Control relay for a normally running fan

Zone 5 is the associated Air Duct Smoke circuit

Zone 15 is the associated Fan Control switch circuit with ...

Z15D (band B2) = "Fan Off"

Z15M (band B1) = "Fan On"

Z15N (bands B3, B4) = "Auto"

Note that the zone range facility is useful in programming controls where selective, automatic switching is required. E.g. if zones 1-10 correspond to ducts in levels 1-10 of a building, and the logic requires Relay 5 to operate if Zone 5 is in alarm but zones 1-4 and 6-

10 are not, the equation for R5 above would become:

Page 9-6

5 July 2001

Issue 2.7

Page 170
Image 170
Tyco F3200 manual Example of FAN RUN & Fault Wiring to AZC, Relays

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.