Document No: LT0122

F3200 Installation & Programming Manual

 

Programming

GLOBAL DATA (CONTINUED)

Cause Preview, Alarm Type, Acknowledge State, Number of Alarms.

and when the "AND." key is pressed, the first line changes to:

Full Cause, Alarm Time, Number of Alarms.

The Cause Preview consists of the first section of the Full Cause.

Note: This setting affects ALL events, network or local, shown on the local F3200. It does not affect the format of information sent to other F3200s on a network, or to RDUs. Each of those devices will display alarms consistent with their own programming options and capabilities.

FFCIF option Always flash non-MAF alarm LEDs – enable/disable

This option is available with V2.07 or later software. By default this is disabled. If enabled the zone LED (if any) for a non-MAF zone will flash when a new alarm occurs on the zone. This allows the alarm to appear as an unacknowledged alarm at an RDU which may be showing the alarm in its FF alarm list. At an RDU, each zone can be programmed as to whether it should be entered into the RDU FF alarm list when the zone goes into alarm. This allows the choice of whereabouts in the system particular zone alarms are displayed.

FFCIF option Always send RDU non-MAF FF alarms – enable/disable

This option is available with V2.07 or later software. This is disabled by default.

If enabled, alarms on all zones are sent to the RDU as displayable FF alarms. The RDU then has the choice of which alarms it displays. In V2.06 or earlier software, a displayable FF alarm was sent to an RDU only if the alarm was entered into the F3200’s FF alarm list.

All zones isolated (Standby Operation)

AS1603.4 suggests that the Standby relay should de-energise if all zones are isolated. This function may be disabled if allowed by the local Fire Brigade.

Brigade Test

Brigade Test normally energises the MAF Alarm relay when the Brigade Test key on the FIP (or RZDU) is pressed for 2 seconds. This function may be disabled if the Fire Brigade does not permit it.

Note that if an output logic equation is programmed for the Alarm relay, (e.g. a special test sequence) this parameter has no effect (except for networked systems). (Refer to BGT token in Section 7.4.3).

For network systems, if the MAF alarm relay is programmed to operate for local brigade test then this also means that the MAF status transmitted onto the network will include a brigade test state of TRUE when a local FIP (or RZDU) brigade test is done. If the local MAF alarm relay is programmed not to operate for local brigade test then the brigade test state transmitted onto the network is always FALSE. If a brigade test state of TRUE is received from another panel on the network and this panel is programmed to use the MAF status of that panel then the local MAF alarm relay and LED will operate regardless of the programming of the local brigade test parameter.

Issue 2.7

5 July 2001

Page 6-25

Page 91
Image 91
Tyco F3200 manual Full Cause, Alarm Time, Number of Alarms, Ffcif option Always flash non-MAF alarm LEDs enable/disable

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.