Tyco F3200 manual Programming Relays

Models: F3200

1 284
Download 284 pages 12.77 Kb
Page 129
Image 129

Document No: LT0122

F3200 Installation & Programming Manual

 

Programming System Configuration

THE OUTPUT LOGIC PROGRAMMING MENUS (CONTINUED)

Open Collectors - 1 to 64 corresponding to the AZC boards installed.

Ancillary Relay - MAF ancillary relays 1,2,3.

Net Var - network variables 1 - 256 (network systems only).

Menu 2

MAF Relay - Standby, Fault, Isolate, Alarm

Zone Isol, Zone De-isol, Zone Reset - these commands can be applied to alarm zones (zones 1-64), module relays (zones 65 - 128), ancillary relays (zones 193-196) and plant (zone 197). These are described in section 7.4.9.

free space - this option is used to display the number of free and used output logic blocks - output logic storage memory is organised into 16 byte blocks.

Menu 3

SNA - for V2.09 or later software, this is used to control the fault sounder. When the equation changes from false to true, the fault sounder is activated and the SOF token becomes true. Pressing any key will silence the sounder. SNA must go false then true again to re-activate the sounder. The fault sounder will also be activated by any conditions in the system that normally activate it.

7.4.7PROGRAMMING RELAYS

When programming relays, the following points should be observed:

1.The default operation of the F3200 MAF Brigade relays conform to AS1603.4. Programming relays for operation, other than default, may contravene the standard.

2.If programming the Alarm relay with a logic equation and it is desired to have it operate during Brigade Test, then the equation entered should include the BGT token. For network systems, note that the ALM token does not include any alarm status received from other panels on the network.

3.Although the MAF Standby relay may be programmed to operate off a logic equation, it is still de-energised (by hardware) for the Battery Very Low condition.

4.If it is desired to use the Plant Isolate option of the "ANCIL ISOL" function menu, all relays to be isolated must include the PLI token in their equations. E.g. R3 = (Z5A + Z6A) . ^PLI.

5.It is not recommended to program normally energised relays because Global Isolate and Plant Isolate de-energise them. Also, they increase FIP quiescent current. All relays have normally closed contacts (i.e. for relay de-energised).

6.If Anc3 has a logic equation entered for it, it no longer operates as "Bells" and is not affected by the "BELLS ISOL" key. The key does still set the BLI token and so, if desired, another relay (e.g. a module relay) could be programmed to operate on a logic equation which includes BEL or BLI (and hence be isolated by "BELLS ISOL").

The BELLS ISOLATED LED operates from BLI and is not affected by the programming of Anc3.

Issue 2.7

5 July 2001

Page 7-27

Page 129
Image 129
Tyco F3200 manual Programming Relays

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.