Tyco F3200 manual Timing, 2 MAF/PSU Inputs, Relay Supervision, Bells Relay

Models: F3200

1 284
Download 284 pages 12.77 Kb
Page 40
Image 40

F3200 Installation & Programming Manual

Document No: LT0122

System Specifications

 

AZC SPECIFICATIONS (CONTINUED)

Timing

 

Standard Delay

2.3 sec (2.0 - 2.6 sec)

(into Alarm, Fault, Normal)

 

AZC Reset

5.3 sec (5.0 - 5.6 sec)

AZC Ignore Period 1

2 sec nom (plus std 2.3 sec delay)

(after Reset)

 

AZC Ignore Period 2

1 sec nom (plus std 2.3 sec delay)

(after Start Up or Programming)

 

AZC Time Into Alarm

Programmable 0-250 sec

AZC Time Out of Alarm

Programmable 0-250 sec

Refer to Section 7.2.4 for detail on other sequences and programmable delays.

3.4.2MAF/PSU INPUTS

Battery Termination

One pair screw terminals; 4sq mm max cable

 

AC Input

31V rms; 3.6A rms; 2.8mm tab terminals

 

Door Switch

5V, 0.5mA, Unsupervised, 4 Way .1" pcb header, J6

 

MCP

5V, 1mA, 2k7 EOLR, 4 Way .1" pcb header, J6

 

Spare Inputs (not fitted)

5V, 0.5mA, Unsupervised, Cabinet internal use only, 4 Way

 

.1" pcb header, J5

 

 

Relay Supervision

 

 

 

Anc 1 Sup/Anc 2 Sup

One screw terminal each

 

Modes of Operation

1 Door holder (Default for Anc 1)

 

 

2 Load (Default for Anc 2)

 

 

Relay Off

Relay On

 

Door Holder Mode expects

Voltage Present

No Voltage Present

 

Load mode expects

Resistive to 0V

Open Circuit or Voltage Present

Voltage Threshold

3.65V Nom

 

 

(Door Holder Mode)

 

 

 

Supervision Current

0mA @ +5V, 1mA @ 0V

 

Load Resistance

400 Ohm - 10k Ohm

 

 

(Load Mode)

less than 400 Ohm with series diode at load.

 

 

14 Ohm absolute minimum.

 

Bells Relay

 

 

 

Form

Reverse polarity - requires series diode at each device

Page 3-12

5 July 2001

Issue 2.7

Page 40
Image 40
Tyco F3200 manual Timing, 2 MAF/PSU Inputs, Relay Supervision, Bells Relay

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.