F3200 Installation & Programming Manual

Document No: LT0122

Programming System Configuration

 

ENTERING EQUATIONS (CONTINUED)

The next relay can be selected. Note that Z9A and Z10A could have been entered as zone range ZR9:10(1)A.

Entering an NA Operand

To enter an NA operand, do the following:

1.Select NA with the in the bottom line and press "ENTER".

2.Select the first token in the "RESET" group with the cursor keys and enter it.

3.Select the next token in the "RESET" group and enter it (the , will automatically be inserted when this token is entered).

4.When all the "RESET" tokens are entered, press one of the Operator keys ("AND", "OR", etc) then enter the "SET" tokens (on the right side of the ;).

5.Select the desired token with the cursor keys.

6.When all the "SET" tokens are entered, press "AND", "OR", "XOR" or "NOT" to exit from NA. If the NA is the last token in an equation and the operand just entered is not required, press "DELETE".

Notes:

1.A logic equation or another NA token cannot be entered directly into an NA operand.

If they are required they must be entered as a variable (i.e. equate a variable to the desired equation).

2.Multiple NA tokens can be used, but each one must be qualified by listing the group of tokens as it is entered. Should the same latch be desired as an operand in various equations, it would be expedient to assign a variable as the NA, and then call up the variable in equations. This saves re-entering the NA with its lists of operands.

7.4.6THE OUTPUT LOGIC PROGRAMMING MENUS

The Output Logic programming menus are shown in Fig 7.1.1 and include the following:

Menu 1

Relay (module relay); Variable; Timer; Open Collector; Ancillary Relay; Net Var;

Menu 2

MAF Relay; Zone Isol; Zone De-Isol; Zone Reset; free space

Menu 3

SNA (sounder activate - software V2.09 onwards)

Menu 1

Relay - this option is used to enter equations for the physical module relays (relay numbers 1 - 64) and to control zone LEDs (relay numbers 65 - 256).

Variable - for variables 1 - 256

Timer - timers 1 to 64 are seconds based and 65 to 72 are minutes based.

Page 7-26

5 July 2001

Issue 2.7

Page 128
Image 128
Tyco F3200 manual Entering an NA Operand, Output Logic Programming Menus

F3200 specifications

The Tyco F3200 series is a sophisticated fire alarm control panel designed for use in various commercial and industrial settings. Renowned for its reliability and ease of use, the Tyco F3200 stands out for its advanced features and state-of-the-art technology, making it a preferred choice for fire safety professionals.

One of the key features of the Tyco F3200 is its modular design, which allows for customization based on specific building requirements. This flexibility enables users to scale the system efficiently, with the capability to connect multiple panels in a network configuration. This adaptability is crucial for large facilities that require comprehensive coverage across expansive areas.

The F3200 utilizes a microprocessor-based control technology that ensures swift processing and response times. This technology enhances the panel's ability to monitor and manage alarms, alerts, and system status, ensuring that users receive real-time updates and notifications in the event of an emergency. The intuitive user interface, characterized by a clear display and user-friendly controls, simplifies the operation process, making it easier for staff to manage the fire alarm system effectively.

Additionally, the Tyco F3200 is compatible with various detection devices, including smoke detectors, heat detectors, and manual pull stations. This compatibility means that the system can be tailored to meet specific safety needs, accommodating a wide array of environments. Furthermore, the panel supports both conventional and addressable devices, providing flexibility in system design.

Another significant advantage of the Tyco F3200 is its advanced communication capabilities. The panel can integrate with various alarm transmission technologies, including RS-232 and RS-485 interfaces, allowing for seamless communication with remote monitoring stations. This feature enhances the reliability of emergency response efforts.

Moreover, the F3200 includes robust diagnostic and reporting tools that help maintenance personnel ensure the system's optimal performance. It provides comprehensive event logs and troubleshooting features, allowing for easy identification of issues and efficient maintenance procedures.

In summary, the Tyco F3200 is an advanced fire alarm control panel that integrates cutting-edge technology, flexibility, and user-friendliness. Its modular design, quick response time, compatibility with various devices, and strong communication capabilities make it an excellent choice for anyone seeking a dependable fire alarm system. Whether for small businesses or large-scale operations, the F3200 delivers essential fire safety solutions tailored to meet the diverse needs of its users.