![SEQUENCE OF OPERATION](/images/new-backgrounds/66130/6613083x1.webp)
MODEL C24EA - ELECTRICAL OPERATION
SEQUENCE OF OPERATION
A.Internal latching relay (ILR) coil on WLC board energizes.
Refer to the correct wiring diagram for model being serviced when reviewing sequence of operation.
NOTE: If power switch is set to off when service voltage is applied, steamer will enter the timed drain cycle.
Basic Model
1.Conditions
A.Steamer connected to correct voltage.
1)120VAC present across X1 & X2 on secondary side of main transformer.
B.Steamer connected to water supply with correct water requirements.
C.Power switch is off (drain handle pulled out).
1)Time delay relay timed out. Timer has no output on terminal 1.
D.Condensate thermostat is open.
E.High limit thermostat closed.
F.Pressure switch is closed.
G.Hold thermostat open.
H.Drain open and steam generator tank (referred to as tank) is empty.
I.Steamer door open.
J.Timer is off.
K.Water level control (WLC) and tank properly grounded.
2.ON/OFF lever pushed in.
A.Manual linkage closes drain valve and operates power switch.
1)N.O. contacts close.
B.Amber power light illuminates.
C.X1 potential to L1 of WLC board.
1)120VAC across L1 & L2 of WLC board.
2)High level coil (HL) energized on WLC board. HL LED on WLC board lights.
3.Slow fill solenoid energized through closure of HL contacts. Tank fills.
4.Water level reaches Low Level
A.LLCO coil is energized. LLCO LED on WLC board lights.
B.LLCO N.O. contacts close enabling heating element circuit.
5.Limiting and regulating contactor coils energize. Power to heating element. Tank water heats.
6.Water level reaches Low level (L) probe.
A.No action as internal latching relay
B.High level (HL) coil
C.Slow fill solenoid
8.Tank water reaches 195E F. Hold thermostat contacts close.
A.Relay K1 energizes. Timer circuit is enabled through closure of N.O. contacts
B.Temperature in tank is maintained at 195E F by hold thermostat control of regulating contactor through relay contacts
9.Timer knob set to time other than zero.
A.Timer motor energized through closure of N.O. contacts
B.Tank temperature maintained by control of regulating contactor coil through N.O. contacts
10.Steamer door is closed.
A.Regulating contactor remains energized as long as time remains on Timer and door is closed.
1)Heating element energized continuously.
11.Temperature of condensate exiting cooking cavity increases to above 135EF.
A.Condensate thermostat closes energizing cooling solenoid 1SOL. Condensate is cooled in drain box before entering facility drain system.
12.Door opened during timed cook cycle.
A.Timer continues count down until time equals zero even if steamer door is opened.
B.Regulating contactor
13.Time reaches zero.
A.Buzzer is energized through N.O. contacts
1)Buzzer remains energized until timer knob is turned to OFF, new time is set or drain handle is pulled out (power switch off).
14.Drain handle pulled out. Tank drains.
A.Power light
7.Water level reaches high level (H) probe.
F25213 (May 2006) |
| Page 42 of 52 |
|