XW System Accessories Installation

Mounting the Unit

The XW Automatic Generator Start is to be mounted vertically on a wall with the connectors facing downwards.

To mount the XW Automatic Generator Start:

1.Hold the unit flush and square against the wall, panel, or horizontal surface.

If the mounting surface requires pre-drill holes for the screws, use the supplied mounting template to mark, then drill, four holes.

2.With a Phillips screwdriver and the supplied #6 screws, secure each corner of the XW Automatic Generator Start to the mounting surface.

Wiring to the 20-contact Connector

CAUTION: Shock Hazard

All installation wiring should be performed by a qualified installer or electrician.

WARNING: Fire, Shock, and Energy Hazards

The 20-contact connector is intended for connection to Class 2 ELV (Extra Low Voltage) circuits only. Do not exceed the circuit limitations specified in the following section.

ELV Circuits

ELV (Extra-Low Voltage) circuits have an open-circuit voltage of not more than 30 Vrms

 

or 42.2 VDC or peak, and are therefore not a shock hazard.

Class 2 Circuits

As per the US National Electrical Code (NEC) and the Canadian Electrical Code (CEC),

 

available power in Class 2 circuits is limited to 100 VA, usually by current limiting by

 

means of overcurrent protection or series resistance. The current is limited to 5 A for

 

circuits with open-circuit voltage of 20 V, and to I=100/Voc for circuits with open circuit

 

voltage between 20 V and 30 V.

 

 

 

Circuit Limitations

The relay contacts in the XW Automatic Generator Start are rated at 5 A maximum and all

 

circuits on the 20-contact connector are rated at 30 V maximum.

 

Ensure that all circuits connected to the 20-contact connector obey the following limits:

 

Table 5-1Circuit Limitations

 

 

 

 

Circuit Parameter

 

Circuit Maximum

 

 

 

 

 

 

 

 

Open circuit voltage (Voc)

 

30 V maximum

 

Overcurrent protection

 

 

 

 

(fuse size for open circuit voltage up to 20 V)

 

5 A maximum

 

 

 

 

 

 

Overcurrent protection

 

5 A to 3.33 A

 

(fuse size for open circuit voltage from 20 V to 30 V)

 

(100/Voc amps

 

 

 

maximum)

 

 

 

 

 

Wiring Harness

Connections to the generator, thermostats, and external ON/OFF switches are made using

 

a wiring harness that plugs into the 20-contact connector (see Figure 5-8).

5–10

975-0239-01-01

Page 102
Image 102
Xantrex Technology XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60 manual Mounting the Unit, 1Circuit Limitations