Inverter/Charger Installation

Step 4: Wiring the Inverter

 

This section provides procedures for making AC and DC connections between the XW

 

Inverter/Charger and the power distribution panel using the cables that are pre-installed in

 

the distribution panel. This section also assumes that the XW Conduit Box was installed in

 

the previous section.

 

For diagrams and information about installing the inverter/charger without the XW

 

Conduit Box and XW Power Distribution Panel, see Appendix C.

 

 

 

 

Important: Communication and signal cables must be segregated from all DC and

 

AC wiring. Therefore, a small raceway has been included in the design of both the

 

XW Power Distribution Panel and the XW Conduit Box to separate the

 

communications cables from the power cables. This is a small raceway run built into

 

the bottom of both the XW Power Distribution Panel and the XW Conduit Box and is

 

held in place by a single screw at the top of the raceway.

 

Installation Tip

Before making the AC or DC cable connections, route the communications cables through

 

the raceway, but do not connect them to their components until after all the inverter

 

connections are made. Once the AC and DC connections are made the run becomes

 

difficult to access. Use different colors for the communications cables (or cable tags) to

 

help make them easier to identify.

Route the communications cables for any accessories being installed BEFORE making AC or DC Connections.

IMPORTANT: When routing communications cables through the XW Power Distribution Panel, the raceway conduit must be used to keep the communications cables separate from the power cables.

XW System

Control Panel

Do not connect to the

XW Automatic Generator Start until all other connections have been made.

XW Automatic

Generator Start

See Figure 2-12 on

 

 

 

page 2–16 for an

Raceway for Communications

Raceway for Communications

illustration showing

Cables*

the Communications

Cables*

 

 

 

Ports and where the

 

*To remove, remove the screws at

accessories connect.

 

the top (Or side) of the raceway.

Do not connect to the XW System Control Panel until all other connections have been made.

Raceway for Shunt Sense cable*. Raceway exits the panel through the back.

Do not connect to the BTS to the batteries until the battery bank has been prepared and is ready to connect to the inverter.

BTS

Figure 2-6Routing Communications Cables

2–8