Specifications

Electrical Specifications

Table A-1XW Power System Electrical Specifications

Model

XW6048-120/240-60

 

XW4548-120/240-60

XW4024-120/240-60

 

 

 

 

 

Continuous Output Power

6,000 W

 

4,500 W

4,000 W

 

 

 

 

 

Surge Rating (10 seconds)

12,000 W

 

9,000 W

8,000 W

 

 

 

 

 

Surge Current

L-n: 105 Arms (7 sec)

 

L-n: 75 Arms (20 sec)

L-n: 70 Arms (7 sec)

 

L-L: 52.5 Arms (7 sec)

 

L-L: 40 Arms (20 sec)

L-L: 35 Arms (7 sec)

Waveform

 

 

True Sine Wave

 

 

 

 

 

 

Idle Consumption—invert mode, no load

28 W

 

26 W

24 W

 

 

 

 

 

Idle Consumption—search mode

 

 

< 8 W

 

 

 

 

 

 

AC Output Voltage

 

 

L-n: 120 Vac ±3%

 

 

 

 

L-L: 240 Vac ±3%

 

 

 

 

AC Input voltage range (Bypass/Charge

 

L-n: 80–150 Vac (120 V nominal)

Mode)

 

L-L: 160–270 Vac (240 V nominal)

 

 

 

 

 

AC Input Current (maximum 75%

L-n: 41.2 A

 

L-n: 30.9 A

L-n: 27.5 A

imbalance between L1-n, L2-n)

L-L: 27.5 A

 

L-L: 20.6 A

L-L: 18.3 A

 

 

 

 

 

AC Input Breaker

 

 

60 A double-pole

 

 

 

 

 

 

AC Input Frequency Range (Bypass/

 

 

55–65 Hz (default)

 

Charge Mode)

 

 

44–70 Hz (allowable)

 

 

 

 

 

 

AC1 voltage range—Sell Modea

 

 

L-n: 108–130 ±1.5 Vac

 

(automatically adjusts when entering Sell

 

 

L-L: 214–260 ±3.0 Vac

 

Mode)

 

 

 

 

 

 

 

 

 

AC1 Frequency range—Sell Modea

 

 

59.4–60.4 ±0.05 Hz

 

(automatically adjusts when entering Sell

 

 

 

 

Mode)

 

 

 

 

 

 

 

 

 

AC Output Current (maximum 75%

L-n: 37.5 A

 

L-n: 28.1 A

L-n: 25.0 A

imbalance between L1-n, L2-n)

L-L: 25.0 A

 

L-L: 18.8 A

L-L: 16.7 A

 

 

 

 

 

AC Output Breaker

 

 

60 A double-pole

 

 

 

 

 

 

AC Output Frequency

 

 

60.0 ±0.1 Hz

 

 

 

 

 

Total Harmonic Distortion

 

< 5%

 

 

 

 

 

 

Automatic Transfer Relay

 

 

60 A

 

 

 

 

Auxiliary Relay Output

 

0–12 Vdc, maximum 250 mA DC

 

 

 

 

 

CEC Weighted Efficiency

93.5%

 

93%

91%

 

 

 

 

 

CEC Power Rating

6,000 W

 

4,500 W

4,000 W

 

 

 

 

 

DC Input Voltage (Nominal)

50.4 Vdc

 

50.4 Vdc

25.2 Vdc

 

 

 

 

 

DC Input Voltage Range

44–64 Vdc

 

44–64 Vdc

22–32 Vdc

 

 

 

 

 

DC Current at Rated Power

127 A

 

95 A

171 A

 

 

 

 

 

Continuous Charge Rate at L-L voltage

100 A

 

85 A

150 A

 

 

 

 

 

Power Factor Corrected Charging

 

 

PF (0.98)

 

 

 

 

 

 

a.This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single Point of Common Connection

A–2

975-0239-01-01

Page 112
Image 112
Xantrex Technology XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60 manual Electrical Specifications