The XW Automatic Generator Start

Connecting an External ON/OFF LED

Wires 9 (White/Blue) and 11 (Black) on the wiring harness can be connected to an LED or other light to accompany a remote external ON/OFF switch. This light turns on when the generator run signal is active to visually indicate that the generator is running.

Important: With some generators, the generator run signal becomes active during the preheat stage, before the generator is actually running. In this case, the external ON/OFF LED (and the Generator On light on the XW Automatic Generator Start) will turn on during the preheat stage and remain on when the generator is running.

For some generators, these lights will also remain on for a period of time after the generator has stopped.

 

2K

 

 

7

START PUSH BUTTON

 

2K

 

 

8

STOP PUSH BUTTON

 

5K11

 

 

9

EXTERNAL LED

 

10

12V OR 24V

 

 

EXTERNAL LED

 

11

 

XW Automatic Generator Start

 

 

13

GROUND

Figure 5-10

External On/Off Switch and LED Wiring Diagram

 

975-0239-01-01

5–15