Step 4: Wiring the Inverter
AUX Port
The XW Series has a 12 Vdc auxiliary output that can be configured to trigger in response to one of the following battery conditions:
•low battery voltage
•high battery voltage
•low battery temperature
•high battery temperature
•any device fault
The auxiliary output can also be triggered manually.
The 12 Vdc output can be used to trigger a relay to disconnect batteries from the inverter/ charger when battery voltage or temperature are out of the ideal range.
The auxiliary output is designed to provide the following functions:
•Auxiliary 12 Vdc power supply
•Remote Power Off
AUX Port
Figure 2-18 AUX Port Location
AUX+12V Voltage Supply
DC voltage is available between
(3 watts).
AUX+12 V and
AUX +12 V voltage supply can be programmed for different tasks ON and OFF using the XW System Control Panel.
Default status of AUX+12 V is OFF.