Xantrex Technology XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60 manual Battery Circuit

Models: XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60

1 136
Download 136 pages 52.84 Kb
Page 86
Image 86

XW Solar Charge Controller Installation

Table 4-3

Recommended Circuit Breakers for the XW Solar Charge Controller

 

Xantrex Part

 

Number

 

Description

 

 

 

865-1065

 

Master Pack - Qty 6, Breaker 250A, 160 Vdc, Stud Terminal, Panel

 

 

Mount, UL/CSA

865-1070

 

Master Pack - Qty 12, Breaker 80A, 125 Vdc, Panel Mount, UL/CSA

865-1075

 

Master Pack - Qty 48, Breaker 60A, 160 Vdc, Panel Mount, UL/CSA

 

 

 

Battery Circuit

The DC-rated fuse or circuit breaker between the battery and the XW Solar Charge Controller must have a maximum size of 1.25 × 60 A (the maximum current rating of the XW Solar Charge Controller). That is, the fuse or circuit breaker must be rated equal to or above 75 A.

 

PV Circuit

 

The DC-rated fuse or circuit breaker between the PV array and the XW Solar Charge

 

Controller must be rated for the Isc of the array but will not exceed the 60 A rating.

Long-distance wire

If there is a significant distance between the PV array and the XW Solar Charge Controller

runs

or between the XW Solar Charge Controller and the battery, larger wires can be used to

 

reduce the voltage drop and improve performance. Refer to Table 4-4 or Table 4-5.

 

 

WARNING: Equipment damage

 

 

Do not connect an array capable of delivering over 60 A Isc to the XW Solar Charge Controller.

 

 

Wires larger than #6 AWG can be used only to reduce power loss in the wiring.

 

 

 

 

 

To use a larger size wire, use a splicer block (terminal block) approved and rated for this

 

 

application. This allows the larger cable size from the batteries to be “spliced” to the #6

 

 

AWG wire connected to the XW Solar Charge Controller. The splicer block must be

 

 

installed outside of the XW Solar Charge Controller wiring compartment.

 

 

Follow manufacturer’s recommendations for torque and mounting. Splicer blocks and

 

 

split-bolt kerneys are available from renewable energy suppliers.

 

 

 

 

 

Important: Local and national electrical codes must be followed for determining additional

 

 

installation requirements.

 

 

Larger wire sizes may be used to improve performance, but may not be installed directly into this

 

 

Charge Controller. Use a splicer block as previously described.

Maximum one-way

Refer to Table 4-4 or Table 4-5 and find the maximum current in the left column, and the

distance and wire

one-way distance from the PV array to the XW Solar Charge Controller (or the distance

size

from the XW Solar Charge Controller to the battery) on the same line, then read the wire

 

 

size required at the top of the column.

4–10

975-0239-01-01

Page 86
Image 86
Xantrex Technology XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60 manual Battery Circuit, PV Circuit