Inverter/Charger Installation
Parts List for Dual-Inverter Configurations
Installing an additional inverter using the power distribution panel requires an XW
Connection Kit (part number
•XW Conduit Box
•Three 60 amp, 120/240 VAC,
•Four Power Distribution bars
•Custom Bypass Interlock
•#6 AWG AC wiring to connect the inverter to AC breakers
•GJ250A, 160VDC, 3/8" Stud, DC Breaker with copper bus bar for DC positive
•one pair #4/0 battery cables to connect the inverter to DC breakers
•Xanbus and AC Sync Cable (CAT 5 cable with RJ45 connectors wired to T568A standard).
•Miscellaneous bushings
Important: When installing more than one inverter at a location, a XW System Control Panel will be required to give each inverter (as well as other
Converting a
◆Remove upper wire cover and lower wire cover on the XW Power Distribution Panel.
DC Wiring for a Dual-Inverter System
1.Remove positive distribution plate attached to bottom terminal on existing DC disconnect/breaker.
2.Install second DC disconnect/breaker (supplied in
3.Replace the
4.Connect positive battery cable for second inverter (supplied in
5.Connect negative battery cable for second inverter (supplied in
6.Connect positive and negative battery cables to second inverter.
7.Remove knockout on the lower cover for additional disconnect/breaker to fit through.