XW System Accessories Installation
Table | Contact Numbers and Functions (Continued) |
| |
|
|
| |
Wire |
|
| Wiring Harness |
Number |
| Function | Wire Color |
|
|
|
|
7 |
| External manual on input | White/Green |
|
|
|
|
8 |
| External manual off input | White/Red |
|
|
|
|
9 |
| External ON/OFF LED Indicator output | White/Blue |
|
|
|
|
10 |
| Constant 12/24 V B+ (battery positive) for External ON/OFF/LED | Red |
|
| Indicator |
|
|
|
|
|
11 |
| External ON/OFF/LED Indicator return (connected internally to | Black |
|
| wire number 13) |
|
|
|
|
|
12 |
| Generator run signal (switched B+) sense input | Violet |
|
|
|
|
13 |
| Generator run signal (switched B+) sense return (generator battery | Black |
|
| negative) |
|
|
|
|
|
14 |
| Relay 1 (Generator run/stop) Normally open contact | Blue |
|
|
|
|
15 |
| Relay 1 (Generator run/stop) Normally closed contact | White/Violet |
|
|
|
|
16 |
| Relay 1 (Generator run/stop) Common contact | Gray |
|
|
|
|
17 |
| Relay 2 (Generator start) Normally open contact | White |
|
|
|
|
18 |
| Relay 2 (Generator start) Common contact | Gray |
|
|
|
|
19 |
| Relay 3 (Preheat/cooldown) Normally open contact | Brown |
|
|
|
|
20 |
| Relay 3 (Preheat/cooldown) Common contact | Gray |
|
|
|
|
Connecting the Generator
To connect the XW Automatic Generator Start to a generator, you must identify the start wiring configuration of the generator you want to use. Generators must be
If the generator is equipped for remote operation, you must examine the wiring of the remote cable and connector (or read your generator’s documentation, if available) and identify the following wires:
| • | Ground |
| • | Start |
| • | Stop |
| • Generator run signal, also known as the Hour Meter or Switched B+ (battery positive) | |
Wiring | To wire the XW Automatic Generator Start to the generator, you need #16 or #18 AWG | |
requirements | wire connected between contacts 12 to 20 on the wiring harness. How many of these wires | |
| you connect and in which combination depends on your generator type. | |
Generator types | The XW Automatic Generator Start has 13 preset generator configurations, or “Gen | |
| Types” (see the XW Automatic Start Owner’s Guide for details on Generator Types). To | |
| ensure that the XW Automatic Generator Start is compatible with your generator’s starting | |
| circuitry, you must select your type of generator from the XW Automatic Generator Start | |
| menu on the XW System Control Panel after completing the installation. |