Xantrex Technology XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60 Wiring the Inverter

Models: XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60

1 136
Download 136 pages 52.84 Kb
Page 39
Image 39

Step 4: Wiring the Inverter

CAUTION: Damage to Equipment

Do not put anything between the battery cable lug and the terminal surface. Overheating of the terminal may occur. Do not apply any type of antioxidant paste until after the battery cable wiring is tightened. The same applies for all DC connections. Do not over-tighten; observe all recommended torque values.

CAUTION: Reverse Polarity Damage

Before making the final DC connection or closing the DC breaker or disconnect, check cable polarity at both the battery and the inverter/charger. Positive (+) must be connected to positive (+). Negative (–) must be connected to negative (–).

Reverse polarity damage is not covered by warranty.

Actual cable requirements may vary.

XW Power Distribution Panel

(shown with door and front panel removed.)

B

See Table 2-8 on page 2–11 for torque values for the Positive and Negative Bus in the XW Power Distribution Panel.

B

C

See Table 2-10 on page 2–11 for torque values for the Battery Connections to the Positive and Negative Bus in the XW Power Distribution Panel.

A

A

C

See Table 2-6 on page 2–10 for torque values for the inverter battery connections.

Torque connections to the battery terminals according to the battery manufacturer’s recommendations.

Figure 2-11DC Connections to a Single Inverter Using a XW Power Distribution Panel

975-0239-01-01

2–15

Page 39
Image 39
Xantrex Technology XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60 manual Wiring the Inverter