XW Solar Charge Controller Installation
WARNING: Explosion/Corrosion Hazard
To reduce the risk of fire or explosion, do not install the XW Solar Charge Controller in sealed compartments containing batteries or in locations that require
To reduce the risk of corrosion from
If using “sealed” batteries, the controller can be mounted in the same enclosure as long as it is adequately ventilated.
For optimal and safe operation, ensure there is adequate clearance around the XW Solar Charge Controller. See Table
Table |
| Minimum Clearance Requirements | |||||||||||
Location |
| Minimum Clearance | |||||||||||
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Above |
| 6 inches (150 mm) When units are mounted to the side of the power distribution | |||||||||||
|
| panel in a vertical stack, the topmost unit must maintain the minimum clearance to | |||||||||||
|
| the nearest surface. | |||||||||||
In front |
| Sufficient room to allow for easy access to read the display, to prevent accidental | |||||||||||
|
| contact with the heat sink, and to perform maintenance. | |||||||||||
On sides |
| 6 inches (150 mm) on at least one side of the overall assembly. A maximum of two | |||||||||||
|
| units can be mounted side by side or side mounted against the power distribution panel. | |||||||||||
|
| In both configurations, the minimum clearance around the outermost unit must be | |||||||||||
|
| maintained. | |||||||||||
|
|
| 6 inches (150 mm) on top and side(s) | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|