Troubleshooting
Failure code(from receive board) | Failure code(from wired Failure code(from | Trouble shooting | Possible reasons | |||
|
| controller) | panel controller) |
|
| |
Flash times of | Flash times of |
|
| |||
Timing LED(or | Running LED(or |
|
|
|
| |
indoor PCB LED4) | indoor PCB LED3) |
|
|
|
| |
|
|
|
|
|
| |
0 | 1 | 01 | E1 | Temperature sensor Ta faulty | Sensor disconected,or broken,or | |
|
|
|
|
| at wrong position,or short circuit | |
|
|
|
|
|
| |
0 | 2 | 02 | E2 | Temperature sensor Te faulty | Sensor disconected,or broken,or | |
|
|
|
|
| at wrong position,or short circuit | |
|
|
|
|
|
| |
0 | 4 | 04 | F8 | EEPROM WRONG | Faulty indoor unit PCB | |
|
|
|
|
|
| |
0 | 7 | 07 | E9 | Abnormal communication | Wrong connection,or the wires be | |
|
|
|
| between indoor and outdoor | disconected,or wrong address | |
|
|
|
| units | setting of indoor unit,or faulty | |
|
|
|
|
| power supply or faulty PCB | |
|
|
|
|
|
| |
0 | 8 | NO EEROR | E8 | Abnormal communication | Abnormal communication between | |
|
| CODE DISPLAY |
| between indoor wired controller | indoor wired controller and indoor | |
|
|
|
| and indoor unit PCB | unit PCB | |
|
|
|
|
|
| |
0 | 12 | 0C | E0 | Drainage system abnormal | Pump motor disconnected,or at | |
|
|
|
|
| wrong position,or the float switch | |
|
|
|
|
| broken down,or the float switch | |
|
|
|
|
| disconected,or at wrong position. | |
|
|
|
|
|
| |
0 | 13 | OD | EF | Zero cross sigal wrong | Zero cross sigal detected wrong | |
|
|
|
|
|
| |
0 | 16 | 10 | F3 | Indoor mode abnormal | Different from outdoor unit mode | |
|
|
|
|
|
| |
2 | 1 | 15 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
2 | 2 | 16 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
2 | 4 | 18 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
2 | 5 | 19 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
2 | 7 | 1B | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
2 | 8 | 1C | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
2 | 9 | 1D | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
3 | 0 | 1E | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
3 | 1 | 1F | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
3 | 2 | 20 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
3 | 3 | 21 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
3 | 5 | 23 | / | Outdoor unit abnormal | Refer to the outdoor unit trouble | |
|
|
|
|
| ||
3 | 6 | 24 | / | Outdoor unit abnormal | shooting | |
|
|
|
|
| list | |
3 | 7 | 25 | / | Outdoor unit abnormal | ||
| ||||||
|
|
|
|
|
| |
3 | 8 | 26 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
3 | 9 | 27 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
4 | 3 | 2B | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
4 | 4 | 2C | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
4 | 7 | 2F | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
4 | 8 | 30 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
4 | 9 | 31 | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
5 | 8 | 3A | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
5 | 9 | 3B | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
6 | 3 | 3F | / | Outdoor unit abnormal |
| |
|
|
|
|
|
| |
6 | 4 | 40 | / | Outdoor unit abnormal |
|
1. For the indoor failure,only running LED ON remote receiver will indicate.
2. For the outdoor failure,timer LED and running LED will indicate.timer LED of remote receiver stands for ten's place,and running LED stands for one's place.timer LED will flash firstly,2 seconds later,running LED will flash too. Afer that,4 seconds later,they will flash in turns again.Flash times equals to the failure code of outdoor plus.
20.For example,failure code of outdoor is 2,the indoor unit should display 22.As a result,timer LED flashes twice firstly,then running LED flashes twice. 3.To get much more details of outdoor unit failure,Please refer to the the outdoor unit trouble shooting list.
15