3. Installing the indoor unit

 

 

(inch)

 

120

 

7/32

 

120

*6-

 

 

3-17/32 3-15/16 3-15/16 3-17/32

 

 

3-15/16

5-1/8

 

70°

*6-3/32

*6-9/16

 

13-25/32

 

 

Fig. 3-4

 

 

3.4. Branch duct hole and fresh air intake hole (Fig. 3-4)

At the time of installation, use the duct holes (cut out) located at the positions shown in Fig3-4, as and when required.

A fresh air intake hole for the optional multi function casement can also be made.

Note:

The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement.

When installing the optional multi function casement, add 135 mm, 5-5/16 inch to the dimensions marked on the figure.

When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.

Branch duct hole

14-ø2.8 mm, ø1/8 inch burring hole

Indoor unit

ø150 mm, ø5-29/32 inch cut out hole

Fresh air intake hole

ø175 mm, ø6-7/8 inch burring hole pitch

Drain pipe

Fresh air intake hole diagram

Refrigerant pipe

3-ø2.8 mm, ø1/8 inch burring hole

Branch duct hole diagram

ø125 mm, ø4-29/32 inch burring hole pitch

(view from either side)

ø100 mm, ø3-15/16 inch cut out hole

 

Ceiling

3.5. Suspension structure (Give site of suspension

strong structure) (Fig. 3-5)

Unit

(inch)

• The ceiling work differs according to the construction of the building. Building

Grille

Pillar

 

23-

 

13/16

 

-57/64

 

31

Ceiling

Use inserts rated at 100-150 kg, 220

Rafter

-331 lbs each (procure locally)

Beam

Suspension bolts M10 (3/8") (procure

Roof beam

locally)

 

Steel reinforcing rod

constructors and interior decorators should be consulted for details.

(1)Extent of ceiling removal: The ceiling must be kept completely horizontal and

the ceiling foundation (framework: wooden slats and slat holders) must be rein- forced in order to protect the ceiling from vibration.

(2)Cut and remove the ceiling foundation.

(3)Reinforce the ends of the ceiling foundation where it has been cut and add ceil- ing foundation for securing the ends of the ceiling board.

(4)When installing the indoor unit on a slanted ceiling, attach a pillar between the ceiling and the grille and set so that the unit is installed horizontally.

Wooden structures

Use tie beams (single storied houses) or second floor beams (two story houses) as reinforcing members.

Wooden beams for suspending air conditioners must be sturdy and their sides must be at least 6 cm, 2-3/8 inch long if the beams are separated by not more than 90 cm, 35-7/16 inch and their sides must be at least 9 cm, 3-9/16 inch long if the beams are separated by as much as 180 cm, 70-7/18 inch. The size of the suspension bolts should be ø10 (3/8"). (The bolts do not come with the unit.)

Ferro-concrete structures

 

Min. 1-3/16

 

9/64)

+3/16 0

(9-2

-1/8

11/16

4

Fig. 3-6

Fig. 3-5

 

Suspension bolt

(inch)

 

Ceiling

 

 

Nut

 

 

Washer (with insulation)

 

 

Mounting plate

 

 

Washer (without insulation)

 

 

Check using the Installation gauge

 

+3/16

0

 

A=11/16

 

Main unit

Ceiling

Gauge

Ceiling opening dimensions

Fig. 3-7

Main unit

Ceiling

Installation template (top of the package)

Screw with washer (Accessory)

Secure the suspension bolts using the method shown, or use steel or wooden hangers, etc. to install the suspension bolts.

3.6. Unit suspension procedures (Fig. 3-6)

Suspend the main unit as shown in the diagram.

Figures given in parentheses represent the dimensions in case of installing optional multi function casement.

1.In advance, set the parts onto the suspension bolts in the order of the washers (with insulation), washers (without insulation) and nuts (double).

Fit the washer with cushion so that the insulation faces downward.

In case of using upper washers to suspend the main unit, the lower washers (with insulation) and nuts (double) are to be set later.

2.Lift the unit to the proper height of the suspension bolts to insert the mounting plate between washers and then fasten it securely.

3.When the main unit can not be aligned against the mounting hole on the ceiling, it is adjustable owing to a slot provided on the mounting plate.

Make sure that A is performed within 17-22 mm, 11/16 to 7/8 inch. Damage could result by failing to adhere to this range. (Fig. 3-7)

Caution:

Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior to installation of the decorative cover or when applying ceiling materials.

3.7. Confirming the position of main unit and tightening the suspension bolts (Fig. 3-8)

Using the gauge attached to the grille, ensure that the bottom of the main unit is properly aligned with the opening of the ceiling. Be sure to confirm this, otherwise

condensation may form and drip due to air leakage, etc.

• Confi rm that the main unit is horizontally levelled, using a level or a vinyl tube

fi lled with water.

• After checking the position of the main unit, tighten the nuts of the suspension

bolts securely to fasten the main unit.

• The installation template (top of the package) can be used as a protective sheet to

prevent dust from entering the main unit when the grilles are left unattached for a

while or when the ceiling materials are to be lined after installation of the unit is fin-

Fig. 3-8

ished.

*As for the details of fitting, refer to the instructions given on the Installation tem- plate.

4

Image 4
Contents Air-Conditioners Contents Safety precautionsInstallation location Installing the indoor unitCheck the indoor unit accessories Fig Refrigerant and drainage piping locations of indoor unitUnit suspension procedures Fig Branch duct hole and fresh air intake hole FigSuspension structure Give site of suspension Strong structure FigInstalling the refrigerant piping PrecautionsConnecting pipes Fig For devices that use R410A refrigerantDrainage piping work Indoor unit FigFor twin/triple combination Drainage piping work FigIndoor unit power supplied from outdoor unit Electrical workFor wired remote controller Remote controllerFor wireless remote controller Function settings Function setting on the unit Selecting the unit functionsFunction setting on the remote controller Assigning a remote controller to each unitSelect unit number Mode Settings Mode no SettingMode Settings Mode no Explanation of wordProcess for setting Operation buttons During the fixed airflow direction modeTo cancel Fixed airflow direction mode How to find air conditioner No To clear fixed settingProcess to find air conditioner No To check refrigerant address No. and unit NoTest run Before test runTest run Self-checkOutput pattern B Check codeWhen electric work is not completed When electric work is completedCheck of drainage Fig Installing the grille System controlTemporary installation of the grille Fig Wire connection FigLocking the up/down airflow direction Fig CheckEasy maintenance function For PUZ-A/PUY-A application only Installing the intake grille FigDisplay example Comp discharge temperature Stable operationPage Index Consignes de sécuritéEmplacement pour l’installation Installation de l’appareil intérieurConsulter le manuel d’installation de l’appareil extérieur PoucesInstallation de l’appareil intérieur Méthodes de suspension de l’appareil FigInstallation de la tuyauterie du réfrigérant ConsignesConnexion des tuyaux Fig Pour les appareils utilisant le réfrigérant R410AMise en place du tuyau d’écoulement Appareil intérieur FigPour double/triple combinaison Mise en place du tuyau d’écoulement FigInstallations électriques SystèmePour la télécommande filaire TélécommandePour la télécommande sans fil Consulter le mode d’emploi de l’appareil intérieur 2. Réglage des fonctions sur la commande à distanceRéglage des fonctions Explication des termes Tableau des fonctionsProcédé de réglage Courantfixed d’airairflowfi xe direction modeClimatiseur et la sortie à régler FluxFlowdeofprocédureprocedure Comment trouver les numéros du climatiseurProcédé pour trouver le numéro du climatiseur Pour effacer les réglagesMarche d’essai Marche d’essaiAuto-vérification Télécommande E0, E3 Erreur de transmission de la télécommandeE1, E2 Erreur du panneau du contrôleur de la télécommande Schéma de sortie BSi l’installation électrique n’est pas terminée Une fois l’installation électrique terminéeVérification de l’écoulement Fig Installer la grille Contrôle du systèmeVérification Mise en place provisoire de la grille FigFixation de la grille Fig 4. Câblage FigExemple d’affichage température de décharge du comp F Installation de la grille d’aspiration FigFonctionnement stable Stable operation Page Contenido Medidas de SeguridadInstalación de la unidad interior Lugar en que se instalaráComprobación de los accesorios de la unidad in- terior Fig Estructura de suspensión Refuerzo de la estruc Tura de suspensión FigProcedimientos de suspensión de la unidad Fig 23-13/16Instalación de los tubos del refrigerante PrecaucionesTubos de conexión Fig Para aparatos con refrigerante R410ATubería de drenaje Unidad interior FigPara combinaciones dobles/triples Tubería de drenaje FigTrabajo eléctrico SistemaPara el controlador remoto cableado Control remotoPara controlador remoto inalámbrico Ajuste de funciones Ajuste de funciones en el controlador remotorAsignación de un mando a distancia para cada unidad Pulse el botón SET con algún objeto puntiagudoDefinición de términos Tabla de funcionesSeleccione el número de unidad Modo Ajustes AjusteProceso de ajuste Para fijar la dirección del aireCómo encontrar el nº del acondicionador de aire NotaPrueba de funcionamiento Antes de realizar las pruebasPrueba de funcionamiento AutotestCiclo de emisión B ComprobaciónPara información detallada Temperatura anormal del cuerpo de refrigeraciónSi el trabajo eléctrico está terminado Comprobación del drenaje FigSi el trabajo eléctrico no está terminado Sistema de control Instalación de la rejillaComprobación Instalación temporal de la rejilla FigFijación de la rejilla Fig Conexión de cables FigInstalación de la rejilla de admisión Fig Cedure to start this operationPage RG79D307K01

PLA-ABA specifications

Mitsumi Electric, a leading manufacturer in the electronic components sector, has made significant strides in audio equipment with the development of the PLA-ABA, a premium audio amplifier. This device is engineered to deliver exceptional sound quality while integrating advanced technologies that enhance its performance and usability.

One of the standout features of the PLA-ABA is its class-D amplifier architecture. This design ensures high efficiency, allowing the device to operate coolly even under heavy load conditions. The amplifier boasts a power output that can drive a wide range of speaker systems, making it suitable for both casual listeners and audio professionals. With a total harmonic distortion (THD) level that is notably low, users can experience pristine audio reproduction without the unwanted artifacts that often plague lower-quality amplifiers.

In addition to its robust performance characteristics, the PLA-ABA is equipped with advanced digital signal processing (DSP). This technology allows for various audio enhancement features, including equalization settings that can be adjusted to suit different musical genres or personal preferences. The user-friendly interface makes it easy to navigate through these settings, ensuring that users can customize their audio experience effortlessly.

Connectivity is another facet where the PLA-ABA excels. It supports multiple input options, including AUX, optical, and Bluetooth, making it versatile for various setups, whether for home theater systems or portable use. The integration of Bluetooth technology not only enables wireless streaming from smartphones and tablets but also ensures a stable connection with minimal latency, making it perfect for both music streaming and gaming.

Durability is paramount in the design of the PLA-ABA. The chassis is constructed from high-grade materials that not only provide a sleek aesthetic but also protect internal components from electromagnetic interference and physical damage. This attention to ruggedness makes the amplifier suitable for both stationary and mobile applications.

Moreover, Mitsumi has placed a strong emphasis on energy efficiency with the PLA-ABA. The device incorporates features that help reduce power consumption when not in use, contributing to a smaller carbon footprint, while still delivering the high-quality audio performance that users expect.

In summary, the Mitsumi electronic PLA-ABA represents a blend of cutting-edge technology and practical design, making it a formidable choice for audiophiles and casual users alike. Its combination of class-D amplification, advanced DSP, versatile connectivity options, and durable construction positions it as a leading product in its category, setting a benchmark for future audio amplifiers.