Installation & Operation Manual
4 Sidewall direct venting (continued)
Multiple vent/air terminations
1.When terminating multiple Knight wall mount boilers terminate each vent/air connection as described in this manual (FIG.
WARNING All vent pipes and air inlets must terminate at the same height to avoid possibility of
severe personal injury, death, or substantial property damage.
2.Place wall penetrations to obtain minimum clearance of 12 inches between edge of air inlet and adjacent vent outlet, as shown in FIG.
3.The air inlet of a Knight wall mount boiler is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent boiler vents.
Figure 4-5A Multiple Vent Terminations (must also comply with Figure 4-1A)
12" MIN. BETWEEN EDGE OF AIR INLET AND ADJACENT VENT OUTLET
VENT
Figure 4-5B Alternate Multiple Vent Terminations w/Field Supplied Fittings (must also comply with Figure 4-1B)
AIR
VENT / AIR
TERMINATION
25