6 Hydronic piping
Near boiler piping components
1. | Boiler system piping: |
|
| |
| Boiler system piping MUST be sized per the pipe | |||
| requirements listed in Table 6A. Reducing the pipe size | |||
| can restrict the flow rate through the boiler, causing | |||
| inadvertent high limit shutdowns and poor system | |||
| performance. Flow rates are based on 20 feet of piping, | |||
| 4 - 90° elbows, and 2 - fully ported ball valves. |
| ||
2. | Boiler circulating pump: |
|
| |
| A Grundfos | |||
| factory (for standard altitude models) as the boiler | |||
| circulation pump based on 20 feet of piping, 4 - 90° | |||
| elbows, and 2 - fully ported ball valves. |
| ||
| Knight wall mount boilers are capable of controlling a | |||
| variable speed | boiler circulator. | Variable | speed |
| circulators MUST be sized to meet the specified | |||
| minimum flow requirements listed in FIG. | |||
| at full speed. |
|
|
|
3. Domestic hot water circulating pump: |
| |||
| Field supplied. The pump MUST be sized to meet | |||
| the specified minimum flow requirements listed in | |||
| FIG. | |||
| guide to determine flow characteristics for the selected | |||
| product used. |
|
|
|
4. | Boiler isolation valves: |
|
| |
| Field supplied. Full port ball valves are required. Failure | |||
| to use full port ball valves could result in a restricted flow | |||
| rate through the boiler. |
|
| |
5. | Check valves: |
|
|
|
| Field supplied. Check valves are recommended for | |||
| installation as shown in FIG.’s | |||
| to install check valves could result in a reverse flow | |||
| condition during pump(s) off cycle. |
|
| |
6. Domestic indirect hot water isolation valves: | ||||
| Field supplied. | Full port | ball valves | are |
Installation & Operation Manual
11.Boiler purge valve:
Field supplied. The boiler purge valve is used to remove entrapped air from the heat exchanger during
12.System temperature sensor:
Lochinvar supplies a system temperature sensor. The sensor is to be installed in the heating loop downstream from the boiler hot water piping and heating loop junction. Typically the sensor will be located far enough downstream to sense system diluted water temperature.
13.Indirect water heaters:
The Knight wall mount boiler may be piped to an indirect water heater to heat domestic hot water with the space heat transfer medium. As depicted in the piping diagrams on page 40 thru 47, there are two options when utilizing an indirect water heater.
A.The space heating piping will branch off to flow the space heat transfer medium through a single wall heat exchanger coil inside the indirect water heater.
B.The indirect water heater is connected to the system supply piping. A pump controlled by the Knight (wall mount) boiler’s control will regulate the flow of water through the indirect water heater. The indirect water heater’s temperature will be regulated by the Knight (wall mount) boiler’s control.
The Knight wall mount boiler is
Lochinvar offers the Squire which is a series of indirect water heaters. The Squire features a stainless steel vessel with a single wall stainless steel heat exchanger.
| required. Failure to use full port ball valves could | |
| result in a restricted flow rate through the boiler. | |
7. |
| |
| Field supplied. | An |
| recommended when storing domestic hot water above | |
| 115°F. |
|
8. | Unions: |
|
| Field supplied. Recommended for unit serviceability. | |
9. | Temperature and pressure gauge: | |
| Factory supplied. The temperature and pressure gauge is |
WARNING
The National Standard Plumbing Code, the National Plumbing Code of Canada and the Uniform Plumbing Code limit the pressure of the heat transfer fluid to less than the minimum working pressure of the potable water system up to 30 psi maximum. Also, the heat transfer fluid must be water or other
shipped loose. It is the responsibility of the contractor to |
install the temperature and pressure gauge on the boiler |
water outlet. |
10. Pressure relief valve: |
Factory supplied. The pressure relief valve is sized to |
ASME specifications. |
14.Y-Strainer:
Field supplied. A