Installation & Operation Manual
1 Determine boiler location
Installation must comply with:
•Local, state, provincial, and national codes, laws, regulations, and ordinances.
•National Fuel Gas Code, ANSI Z223.1 – latest edition.
•Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME
•National Electrical Code.
•For Canada only: B149.1 Installation Code, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.
NOTICE | The Knight wall mount boiler gas | |
manifold and controls met safe lighting | ||
| ||
| and other performance criteria when the | |
| boiler underwent tests specified in ANSI | |
| Z21.13 – latest edition. |
Before locating the boiler, check:
WARNING
WARNING
This appliance is certified as an indoor appliance. Do not install the appliance outdoors or locate where the appliance will be exposed to freezing temperatures or to temperatures that exceed 100°F.
Failure to install the appliance indoors could result in severe personal injury, death, or substantial property damage.
This appliance requires a special venting system. The vent connection to the appliance is made of CPVC. Field supplied vent fittings must be cemented to the CPVC fitting on the boiler. Use only the vent materials, primer, and cement specified in the manual to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.
1. Check for nearby connection to: |
• System water piping |
• Venting connections |
• Gas supply piping |
• Electrical power |
2. Locate the appliance so that if water connections should |
leak, water damage will not occur. When such locations |
cannot be avoided, it is recommended that a suitable |
drain pan, adequately drained, be installed under the |
appliance. The pan must not restrict combustion air |
flow. Under no circumstances is the manufacturer to be |
held responsible for water damage in connection with |
this appliance, or any of its components. |
Closet and alcove installations
A closet is any room the boiler is installed in which is less than 79 cubic feet for WBN051 through WBN106 models, 104 cubic feet for WBN151 models, and 125 cubic feet for WBN211 models.
An alcove is any room which meets the criteria for a closet with the exception that it does not have a door.
Example: Room dimensions = 4 feet long, 4 feet wide, and 9 foot ceiling = 4 x 4 x 9 = 144 cubic feet. This would be considered a closet for a Knight wall mount boiler.
3. Check area around the boiler. Remove any combustible |
materials, gasoline and other flammable liquids. |
Failure to keep boiler area clear and free WARNING of combustible materials, gasoline, and other flammable liquids and vapors can result in severe personal injury, death, or
substantial property damage.
WARNING
For closet and alcove installations as shown in FIG.’s
4. The Knight wall mount boiler must be installed so that gas control system components are protected from dripping or spraying water or rain during operation or service.
5. If a new boiler will replace an existing boiler, check for and correct system problems, such as:
• System leaks causing oxygen corrosion or heat exchanger cracks from hard water deposits.
•
• Lack of freeze protection in boiler water causing system and boiler to freeze and leak.
Provide clearances:
Clearances from combustible materials
1.Hot water
2.Vent pipe – at least 1" from combustible materials.
3.See FIG.’s
Clearances for service access
1.See FIG.’s
7