Installation & Operation Manual
3 General venting
Polypropylene
This product has been approved for use with polypropylene vent with the manufacturers listed in Table 3E.
All terminations must comply with listed options in this manual and be a
For use of flex pipe, it is recommended to have the vent material in 32°F or higher ambient space before bending at installation. No bends should be made to greater than 45° and ONLY installed in vertical or near vertical installations.
For support and special connections required, see the manufacturer's instructions. All vent is to conform to standard diameter and equivalent length requirements established.
WARNING
NOTICE
NOTICE
Use only the adapters and vent system listed in Tables 3E and 3F. DO NOT mix vent systems of different types or manufacturers. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installations must comply with applicable national, state, and local codes. For Canadian installation, polypropylene vent must be listed as a
Installation of a polypropylene vent system should adhere to the vent manufacturer’s installation instructions supplied with the
Table 3E Polypropylene Vent Pipe and Fittings
Approved Polypropylene Vent Manufacturers
Make | Model |
Centrotherm Eco Systems | InnoFlue SW/Flex |
|
|
Duravent (M & G Group) | PolyPro |
|
|
vent system.
NOTICE | The installer must use a specific vent | |
starter adapter at the flue collar | ||
| connection. The adapter is supplied by | |
| the vent manufacturer to adapt to its vent | |
| system. See Table 3F for approved vent | |
| adapters. Discard CPVC starter piece. | |
| All vent connections MUST be secured by | |
NOTICE | ||
the vent manufacturer's joint connector | ||
| (FIG. |
WARNING Insulation should not be used on polypropylene venting materials. The use
of insulation will cause increased vent wall temperatures, which could result in vent pipe failure.
Table 3F Approved PolypropyleneTerminations
Figure 3-8 Near Boiler Polypropylene Venting
JOINT CONNECTOR REQUIRED
AT ALL COMPONENT CONNECTIONS
OF VENT SYSTEM
POLYPROPYLENE ADAPTER
W/FLUE CLAMP
IMG00155
Model | Centrotherm InnoFlue SW |
| Duravent Polypro |
| |||
|
|
|
|
|
|
| |
Polypropylene Adapter / | Joint | Sidewall Retaining | Sidewall | Polypropylene Adapter | Joint | Sidewall Kit* | |
| Flue Clamp | Connector | Bracket* | Adapter* | Connector | ||
ISAG0202 w/IAFC02 | IANS02 | IATP0202 | ISTAGL0202 | ||||
|
|
|
|
|
|
|
|
| ISAG0303 w/IAFC03 | IANS03 | IATP0303 | ISTAGL0303 |
|
* These parts are only needed if the sidewall termination assembly is used (see FIG.
20