Installation & Operation Manual
6 Hydronic piping
Figure 6-2 Pressure Drop vs. Flow - Models 51 - 211
6
Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
|
|
| 20°F Temperature Rise Applications |
|
| |||
Model | GPM | FT/HD | Minimum Pipe |
| Pump |
|
| |
Size | Grundfos | TACO | B & G | Armstrong | ||||
|
|
| ||||||
51 | 5.1 | 11 | 1" | 0011 | E7 | |||
81 | 7.5 | 24 | 1" | 0011 | E7 | |||
106 | 9.8 | 27 | 1" | 0013 | E11 | |||
151 | 14.0 | 20 | 1" | 0011 | E7 | |||
211 | 19.6 | 29 | 1" | E9 |
|
|
| 25°F Temperature Rise Applications |
|
| |||
Model | GPM | FT/HD | Minimum Pipe |
| Pump |
|
| |
Size | Grundfos | TACO | B & G | Armstrong | ||||
|
|
| ||||||
51 | 4.1 | 7.3 | 1" | 0014 | E7 | |||
81 | 5.9 | 15.0 | 1" | 0014 | E7 | |||
106 | 7.7 | 17.5 | 1" | 0014 | E7 | |||
151 | 11.0 | 12.8 | 1" | 0014 | E7 | |||
211 | 15.5 | 19.0 | 1" | 0013 | E7 |
|
|
|
| 35°F Temperature Rise Applications |
|
| ||
Model | GPM |
| FT/HD | Minimum Pipe |
| Pump |
|
|
| Size | Grundfos | TACO | B & G | Armstrong | |||
|
|
|
| |||||
51 | 2.9 |
| 4.1 | 1" | 007 | |||
81 | 4.2 |
| 7.3 | 1" | 007 | |||
106 | 5.5 |
| 9.8 | 1" | 007 | |||
151 | 7.9 |
| 10 | 1" | 008/0010 | |||
211 | 11.0 |
| 10.1 | 1" | 0010 | |||
| Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude | |||||||
NOTICE | ||||||||
|
| models. |
|
|
|
|
| |
|
|
|
|
|
|
| ||
NOTICE | Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude | |||||||
|
| models. |
|
|
|
|
| |
|
|
|
|
|
|
| ||
NOTICE | The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation. |
38