Installation & Operation Manual
12 Maintenance Maintenance and annual startup
Table 12A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
| General: |
|
|
|
|
| • Address reported problems |
| |||
| • Inspect interior; clean and vacuum if | ||||
| necessary; |
|
|
| |
| • Clean condensate trap and fill with fresh | ||||
| water |
|
|
|
|
| • Check | for | leaks (water, gas, | flue, | |
| condensate) |
|
| ||
UP | • Verify flue and air lines in good condition | ||||
and sealed tight |
|
| |||
- |
|
|
|
|
|
START | • Check | system water | pressure/system | ||
| |||||
| piping/expansion tank |
|
| ||
ANNUAL | • Check control settings |
|
| ||
• Check ignition and flame sense |
| ||||
|
| ||||
| electrodes (sand off any deposits; clean | ||||
| and reposition) |
|
| ||
| • Check wiring and connections |
| |||
| • Perform | checkout | and | ||
| performance verification per Section 10 | ||||
| of this manual. |
|
| ||
| • Flame inspection (stable, uniform) |
| |||
| • Flame signal (at least 10 microamps at | ||||
| high fire) |
|
|
| |
| • Clean the heat exchanger if flue | ||||
| temperature is more than 54°F above | ||||
| return water temperature. |
|
If combustion or performance indicate need:
•Clean heat exchanger
•Remove and clean burner using compressed air only
•Clean the blower wheel
Owner maintenance
(see the Knight Wall Mount User’s Information
Manual for instructions)
| • Check boiler area |
Daily | • Check pressure/temperature |
| gauge |
| • Check vent piping | |
| • Check air piping | |
Monthly | • Check air and vent termination | |
| screens | |
| • Check relief valve | |
| • Check condensate drain system | |
| • Check air vents | |
|
| |
Periodically | • Test low water cutoff (if used) | |
• Reset button (low water cutoff) | ||
| ||
|
| |
| • Check boiler piping (gas and | |
Every | water) for leaks | |
| ||
6 months | • Operate relief valve |
End | • Shut boiler down (unless boiler | |
of season | ||
used for domestic hot water) | ||
months | ||
|
73