GE C11, AF-300 manual Connecting the main circuit and ground terminals

Page 19

2-3-2 Connecting the main circuit and ground terminals

Table 2-3-1 Functions of main circuit and ground terminals

Symbol

Name

Explanation

L1/R,L2/S,L3/T

Main power supply input

Connects 3-phase power.(3-phase 230V input)

L1/L,L2/N

Connects single-phase power. (Single-phase 230V input)

 

U, V, W

Drive output

Connects 3-phase motor.

P1, P(+)

For connection of DC

Connects input power- factor correcting DC reactor

 

reactor

(optional).

P(+), N(-)

For DC intermediate circuit

Connected to DC link circuit terminal

 

 

(for DC bus connection).

G

For drive grounding

Ground terminal for drive chassis (case).

(1) Main power supply input terminal

3-phase 230V [L1/R,L2/S,L3/T] Single-phase 230V [L1/L,L2/N]

1Connect the main power supply input terminals to the power supply via a molded case circuit breaker for circuit protection or earth leakage circuit breaker. An earth- leakage circuit breaker which can also detect DC current

is recommended. Phase-sequence matching is unneces- sary.

2It is recommended that a magnetic contactor is connected

to prevent any failure or accident from becoming serious by disconnecting the drive from the power supply when the drive protective function operates.

3Do not turn on or off the main power supply to start or stop the drive; instead, use the control circuit terminal FWD/REV or the RUN/STOP key on the keypad panel. If it is unavoidable to turn the main power supply on or off to start or stop the drive, it must not exceed once per hour.

G L1/R L2/S L3/T P1 P(+)

For 3-phase 230V input

G

L1/L

 

L2/N

P1

P(+)

 

 

 

 

 

 

For single-phase 230V input

AF-300C11

P(+) N(-) U V W G

Figure 2-3-1 Arrangement of

main circuit and ground termi-

nals

(2)Drive output terminal [U, V, W]

1 Connect these terminals to the 3-phase motor with the correct phase-sequence. If a motor rota- tion direction does not correspond to the correct rotation direction, exchange any two of the U, V,

and W phases.

2Do not connect a phase-advance capacitor or surge absorber to the drive output.

3A very long wiring length between the drive and the motor causes a high frequency current to flow due to floating capacity between cables, making the drive trip, increasing the leakage current and deteriorating the accuracy in the current display. To prevent such trouble, the wir- ing length to the motor should not exceed 165 feet (50 m).

When the drive is operated in the low noise mode (carrier frequency: 8 to 15 kHz) and the wir- ing length is long, add an optional output circuit filter.

-17-

Image 19
Contents AF-300 C11 TM Table of Contents Safety Instructions Page Compliance with low voltage directive in EU Otherwise fire could occur Drive may be dropped causing injuryInstructions on use There is a risk of fireOtherwise electric shock could occur Instructions on wiringOtherwise, fire could occur Otherwise electric shock or fire could occurOtherwise burns could occur Instructions on operationOtherwise accident could occur There is a risk of accidentsOtherwise electric shock or injury could occur Instruction on maintenance/inspection, and replacementGeneral instructions Preface GE Product Code AF-300 Drive Family Input Voltage Input PhasesHorsepower Factory Installed Options230VAC, Single phase, 50/60Hz Input 230VAC, 3 phase, 50/60Hz InputReceiving Inspections Before Using This ProductAppearance Handling the Product 1 Storage and transportation environment Storage precautionsCarrying Storage and transportation1 Operating environment Installation and Connection10 cm AF-300C11Connection 1Basic connectionOtherwise electric shock and fire could occur 1 Functions of main circuit and ground terminals Connecting the main circuit and ground terminalsConnection diagram Connecting the control terminalsCutting of barrier -3-2 Connection of DC reactor 4 Surge absorber connection diagram 7 Control terminal block arrangement FWD 2 Functions of control circuit terminalsDX+ Connection examples 200 to 50/60Hz Mccb Fuse Connection to PLC when analog signal is input from PLC Others Harmonic componentNoise Leakage current1 General operation method OperationInspection and Preparation before Operation Operation MethodTrial Run 1 Running commandNames and Functions Keypad PanelIs pressed at the same time as Operating Keypad PanelProcedure Display Press Fundamental functions Selecting FunctionFunction Selection List 1 Table of Function Selection List To 10.0min Carrier freq 75kHz is set when 0 is specified Sound toneVoltage adjust 30Ry operation mode Excited when tripped Normally excitedJump frequency Extension Terminal FunctionsControl Functions of Frequency X3 terminal function TionsHigh Performance Functions Motor ParametersSerial communication option Optional FunctionsOtherwise injuries could occur F00 Data protectionF01 Details of Each FunctionMotor runs when F02 Operation methodKey is pressed and decelerates-to-stop when GE Start Software Selection During Terminal Operation This function sets the maximum output frequency F03 Maximum output frequencyF07 F04 Base frequencyF05 F06F10 F11 Electronic thermal O/L relay Select F09 Torque boostElectronic thermal O/L relayLevel F12 Electronic thermal O/L relay thermal time constant Set with F12 Operating time? ì? ? ŒcharacteristicsÀ ÁF16 Frequency limiter Low F14 Restart mode after momentary power failurePhase input Single Phase Input F15 Frequency limiter HighBias negative 20mAdc F17 Gain For frequency setting signalF18 Bias frequency Bias positiveF21 F20 DC injection brake Starting frequencyF22 DC injection brakeBraking time F26 Motor sound carrier freq F23 Starting frequencyF25 Stop frequency F24F27 Motor sound sound tone F30 FM terminal voltage adjustF31 FM terminal Function Normal Tripped Operation F36 30Ry operation modeX3 terminal function E01 E02 E03X1 terminal function X2 terminal functionFrom previous C04 Jump frequency Hysteresis C07 Multistep frequency settingP00 Motor characteristics C01 C02 C03 Jump frequency 1, 2H02 Trip history H01 Operation timeH03 H04 Auto ResetH20 PID control Mode select Data initializationH25 PID control Feedback filter H21 PID control Feedback signalH22 PID control P-gain H23 PID control I-gainRS485 RTU communication O00 Option selectionOptional RS485 serial communication unit List of protective functions Protective Function1 List of Protective Functions Otherwise fire could occur Alarm ResetKeypad panel Normal display Alarm display Display Alarm output TripCase of tripping TroubleshootingLoad excessive? OvervoltageOU Power supply voltage within specified value?Does OU activate when load is removed Consider using DCHeat sink overheat- ing OH1 Drive overload OLU or motor overload OL Is electronic thermal O/L relay setting correct?Noise source nearby? Probable faulty drive. Contact GE Fuji Set o00 toConnect the input wires correctly Input phase failure Lin and imbalanceMotor does not start Setting too low? When motor rotates but the speed does not changeSet F00 to When motor stalls during accelerationMotor generates ab Function change is disabled Normal heat To 0?There is danger of electric shock Maintenance and InspectionDaily Inspection Periodic InspectionDiscoloration and distortion Visual Not abnormal 1 Periodic inspection listElectrolyte leakage Visual Not abnormal More Overheating? Is off 2Tighten more 3Visual inspection 1 Meter for measuring the main circuit Three-phaseSingle -phase Electrical measurements in the Main CircuitMotor Supply Case of 3-phase input seriesInput series + +Inquiries about Products and Product Warranty Warranty Coverage 6Warranty ServiceIN-WARRANTY Failure Checklist Standard Specifications SpecificationsDrive output capacity kVA at RUN Stop Common specificationsPage Page Page Dimensions 00.2 2 68 17.2 D 00.2 Terminal Terminal 1 M2.5 00.2 2 Built-in Options OptionsExternal Options 1 External Options Connection method Applicable DC reactorsL1/L L2/N L1/R L2/S L3/T P1 + N- U THR CM PrecautionsCompliance with standards GeneralGeneral General Electromagnetic Compatibility EMCRFI Filters Ferrite Ring Dimensions 1 RFI filters DimensionsPage 1 Recommended Installation 2 Recommended installation detail inside the enclosure GE Fuji Drives USA, Inc Roanoke Blvd. Suite