(3) Undervoltage(LU) | (4)Overheating of heat sink (OH1) |
LU
Heat sink overheat- ing (OH1)
| Has (momentary) power fail- | Yes | Reset and restart opera- |
| ||
|
|
|
| |||
| ure occurred? |
|
| tion. (If F14 is 0,1) |
| |
|
|
|
|
|
|
|
|
| No | Yes |
|
| |
|
|
|
|
| ||
| Faulty parts or loose connec- | Replace faulty parts and |
| |||
|
|
|
| |||
| tion in power control circuit? |
|
| fix connection. |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Load excessive?
No
Cooling fan rotating?
Yes
Reduce load.
No | Replace cooling fan. |
| No |
| |
|
| No | |
Power supply voltage within | |||
|
Yes
specified value? |
Yes |
| Any load requiring large | Yes | |
| starting current within the |
| |
| same power distribution |
| |
| group? |
| |
|
|
|
|
|
| No |
|
|
|
| Yes |
| Does LU activate when cir- | ||
|
| ||
| cuit breaker or magnetic con- |
| |
| tractor switched to ON? |
| |
|
|
|
|
|
| No |
|
|
|
|
|
| Probable faulty control circuit |
| |
| of drive or error because of |
| |
| noise, etc. Contact GE Fuji |
| |
|
|
|
|
Modify power distribu- tion system to satisfy specified value.
Power transformer ca- pacity adequate?
Yes
Probable faulty drive. Contact GE Fuji
Cooling air passage blocked up?
No
Ambient temperature within specified value?
Yes
Probable faulty drive or error because of noise, etc. Contact GE
Fuji.
Yes Remove obstacles.
No Arrange peripheral conditions to secure
specified value.
(5) External alarm input (OH2)
OH2
Signal from external de- vice connected between control circuit terminals THR - CM?
Yes
No
Connect alarm signal con- tact.
Is the alarm function of the external device operat-
ing correctly?
Yes
No | Probable faulty drive or | |
error because of noise. | ||
| ||
| Contact GE Fuji. | |
| ||
|
| |
|
|
Remove the cause of alarm function activation.