| Check part | Check item | How to inspect | Evaluation criteria | |
|
| Resistor | 1)Unpleasant smell and crazing | 1)Olfactory and | 1)Not abnormal. |
|
|
| of the insulation by | visual inspection | 2)Less than about ±10% of |
|
|
| overheating | 2)Visual inspection | the indicated |
|
|
| 2)No open circuit? | or use a multimeter | resistance value |
circuit |
|
|
| by removing a |
|
|
|
| connection on one |
| |
|
|
|
|
| |
Main |
|
|
| side. |
|
| Trans- | Abnormal buzzing or unpleasant | Aural, olfactory, and | Not abnormal. | |
|
| ||||
|
| former and | smell? | visual inspection |
|
|
| reactor |
|
|
|
|
| Magnetic | 1)Rattling when operating? | 1)Aural | 1), 2) Not abnormal. |
|
| contactor | 2)Roughness of contact? | 2)Visual inspection |
|
|
| and relay |
|
|
|
|
| Control PC | 1)Loose screws or connectors? | 1)Tighten more. | 1), 2), 3), 4) |
|
| board and | 2)Unpleasant smell or | 2)Olfactory and | Not abnormal. |
circuit |
| connector | discoloration? | visual inspection |
|
|
| 3)Cracks, damage, deformation, or | 3),4)Visual |
| |
|
|
|
| ||
Control |
|
| excessive rust? | inspection |
|
|
| 4)Electrolyte leakage or a |
|
| |
|
|
|
|
| |
|
|
| deformed mark on the |
|
|
|
|
| capacitor? |
|
|
|
|
|
|
|
|
|
| Cooling | 1)Abnormal sound or vibration? | 1)Aural and visual in- | 1)The fan must rotate |
|
| fan | 2)Loose of bolts? | spection. Turn with | smoothly. |
|
| (2 HP or | 3)Discoloration by | hand. (Make sure power | 2), 3)Not abnormal |
system |
| more) | overheating? | is off) |
|
|
|
| 2)Tighten more |
| |
|
|
|
|
| |
|
|
|
| 3)Visual inspection |
|
Cooling |
| Ventilation | Visual inspection | Not abnormal | |
| way | heat sink or intake/exhaust ports? |
|
| |
|
|
|
| ||
|
|
|
|
|
|
(Note) Use a capacitance measuring instrument available on the market which is easy to use. (Remark) If the equipment is stained, wipe it with a cleaning cloth, which is chemically neutral.